To: Wayne Liang
Principle Investigator: Martin Pitasi
Submission Date: 21AUG04
Title: Ballistic Missile Innovative Radar and RF Products
Subtitle: Phase 1 Final Report
References:
a. SBIR Topic No. MDA03-052
b. Proposal Number B031-1925
c. Contract No. N00178-04-C-3046
d. Page 7 of the Technical Information Document, No. R-134a, titled “Thermodynamic
Properties of HFC-134a,” published by Dupont SUVA

Enclosures:
1. Summary of Results
2. Cooling Cycle Flow Diagrams0
3. System Flow Summary
4. Flow Resistance
5. Load Sensitivity
6. Test Fixture and Instrumentation
7. Heat Exchanger
8. Evaporator Test Results
9. Condenser Test Results
10. Heat Exchanger Test Data and Results
11. Pump Reliability

Summary:
The goal of this Phase 1 SBIR study is to demonstrate to the Missile Defense Agency (MDA)
that pumped liquid multi-phase cooling (PLMC) technology offers a superior and credible
alternative to conventional single-phase ethylene glycol/water (EGW) systems. The results
show conclusively that a PLMC system designed as a potential replacement for the EGW
system performs equally well. Primary advantages of the PLMC design are its inherent
isothermal cooling, higher reliability, lower hardware and operating costs, smaller package
envelope, and reduced weight.

Background:
To enhance and augment Phase Array Radar performance, Raytheon requested (Reference a)
that Thermal Form and Function (TFF) submit a proposal to the MDA SBIR program (Reference
b). As a result of this effort, TFF was awarded a Phase 1 contract (Reference c) to compare the
cooling performances of an existing EGW phase-array cooling platform to a similar PLMC
design. In support of the study, design criteria data was leveraged from an existing Raytheon
EGW cooling platform (Enclosure 1).

PLMC technology was developed in 1998 by Thermal Form & Function for cooling Compaq
Computer’s Alpha Server Division, next-generation, Enterprise Servers. The technology was
driven by design constraints beyond the limits of conventional cooling capabilities. Constraints
included maintaining 32, 200 W computer processor packages at operating junction
temperatures below 85 ºC, reliability and safety, package size and weight, and hardware and
operating cost limits. From these constraints, pumped liquid multi-phase cooling (PLMC)
evolved. The PLMC design consists of commercially available hardware that includes a



                                                                                              1
refrigerant pump, air- and water-cooled condensers, distribution manifold, separator, reservoir,
and system controls.
To demonstrate the technology a proof-of-concept system packaged in a standard 18” cabinet
was built and tested. The test data and accompanying results confirmed that the PLMC system
met all the design constraints defined by Compaq Computer.


Since 1998, the technology roadmap has successfully evolved from cabinet cooling to rack, 1U,
and blade designs.
Results:
The summary of the results is shown in Enclosure 1. Listed are Raytheon’s EGW design
constraint values and corresponding reference items. Adjacent to these values are Thermal
Form and Function’s PLMC R-134a system design results. Both values are compared and
shown as a percentage change.
At a heat load of 54.4 kW and a coolant temperature of 30.0 ºC (86.0 ºF), the PLMC design
requires        8.2 gal/min (gpm) of R-134a coolant. This value is 84% lower than the 50 gpm
specified for the EGW platform. Subsequent reductions of 91% and 98 % are reflected in the
system pressure drop and pump horsepower, respectively. Correspondingly, similar changes in
flow and pressure drop are reflected in the EDA manifold section. The critical manifold
temperature for the PLMC design is 34 ºC or 12 % lower the 38 ºC EGW value.
Chilled water provided for cooling the EGW heat exchanger or PLMC condenser will deliver 50
gpm of water at 15.0 ºC (59.0 ºF) and 20.0 psig.
The R-134a pump advantages include a reduction in horsepower and weight requirements.
Horsepower requirements drop from 10, for the EGW pump, to 0.2 for the R-134a pump or 98%.
Correspondingly, the weight change is from 300lb to 25lb or 92% lower.
The potential of electronics failing due to liquid leakage associated with the ethylene
glycol/water cooling system exists and needs to be considered as having a negative impact on
reliability. However, any R-134a leaks occur in the form of a non-toxic, non-ozone depleting,
inert vapor that has no detrimental effect on electronics. Refrigerant pump hardware reliability is
listed as high and is based on 11 failures of unknown origin over 60 million pump hours of
operation (Enclosure 11). No reliability data exist for the EGW pump. Estimated package
volumes for the PLMC design and the EGW platform are16, 875 in3 (25”L x 15”W x 45”H) and
108,000 in3 (60”L x 30”W x 60”H), respectively. Comparing these results shows that the PLMC
design envelope is 84% smaller than the Raytheon platform. Correspondingly, the PLMC
system weight of 150 lb is 83% lighter than the 874 lb Raytheon platform.

This study assumes that the pumps consume 100 % of the parasitic power. Instrument and
control power is considered negligible and have no impact on the results. Pump specification
indicate that the R-134a pump uses 0.12 kW or 98 % less power than the 7.5 kW needed by the
EGW pump.

Hardware costs figures for the Raytheon platform and the PLMC design are $11,340 and
$6500, respectively, or 43% less.

Enclosure 2 details the flow diagrams for the EGW platform and PLMC system design. Figures
1 and 2 show the Raytheon design criteria and PLMC design results, respectively. The EGW
diagram (Figure 1) shows 50 gpm of ethylene glycol/water pumped at 35.0 ºC (95.0 ºF) and
125.0 psig though a water-cooled heat exchanger. The heat exchanger removes 54.4 kW and




                                                                                                 2
reduces the coolant temperature from 35.0 ºC (95.0 ºF) to 30.0 ºC (86.0 ºF). The coolant flows
into the EDA assembly and is uniformly distributed between the manifolds. Approximately 6.3
gpm of coolant passes through each manifold cooling 6.8 kW of EDA power, raising the fluid
temperature from 30.0 ºC to 35.0 ºC. The coolant exits the EDA at 35.0 ºC and 5.0 psig then
flows through the filter prior to entering the pump. Filter and miscellaneous line losses account
for the remaining 5 psig. A reservoir located prior to the filter provides a controlled volume
designed to compensate for any coolant volume change produced by temperature fluctuations.
A motorized valve and temperature sensor control the EGW at 30.0 º C. The valve located in
the water return line of the heat exchanger modulates the flow in response to changes in the
EGW discharge temperature (Figure 1). Reviewing the PLMC cycle (Figure 2) shows 8.2 gpm of
R-134a sub-cooled fluid discharging from the pump at 30.0 ºC (86.0 ºF) and 112.3 psig. The
coolant flows into the EDA assembly and is uniformly distributed between the manifolds.
Approximately 1.0 gpm of coolant passes through each manifold, isothermally cooling 6.8 kW of
EDA power. This design is based on an EDA discharge quality of 50%. The mixture enters the
separator (tube) at 32.0 ºC, 103.4 psig, and 50 % quality. Here gravity causes the saturated
liquid to collect at the tube bottom displacing the saturated vapor. The vapor is condensed to a
sub-cooled liquid leaving the condenser at 28 ºC and 103.4 psig. Prior to the pump both liquids
mix to form a sub-cooled liquid at 30.0 ºC and 103.4 psig. Filter and miscellaneous line losses
account for the remaining 0.5 psig. As in Figure 1 the reservoir compensates for volume
changes due to fluctuation in temperature. In the unlikely event that the R-134a charge is
compromised a sensor located at the top of the bleed line signals a controller to power down the
system. A passive, low cost OEM flow control valve, regulated by pressure, maintains the R-
134a saturation pressure at 103.4 psig or 30 ºC.

Enclosure 3 is a chart showing the system flow summary for R-134a. Included in the chart are
the pump curve, the EDA baseline curve, and EDA design curve. Reviewing the results shows a
system design point (DP) of 9.4 psid at 8.2 gpm (Enclosure1). To achieve the 9.4 psid an
additional 6.3 psid of resistance is added to the 3.1 psid baseline value. The 6.3 psid resistance
is added in the form of manifold metering orifices that augment the flow distribution.

Enclosure 4 details the flow resistance data that characterize the PLMC system design. At the
design flow of 8.2 gpm, Chart 1 shows a corresponding system resistance of 9.4 psid. This
value consists of adding the 6.3 psid metering orifice resistance to the 3.1 psid EDA baseline.
Chart 2 shows both the EGW and R-134a baseline system resistance curves. The R-134a curve
is developed from EGW design criteria of 105 psig at 50 gpm. Extrapolating the R-134a data
from 50 gpm to 8.2 gpm results in a baseline resistance value of 3.1 psid.
Enclosure 5 is a load sensitivity study. Noted in the summary is the design point of 54.4 kW load
and     50 % quality. Typical quality limits for the preferred operating range are 25% and 75%.
The corresponding load limits for this design at 30.0 ºC (86.0 ºF) are 109.6 kW and 37.3 kW,
respectively.
To supplement the SBIR effort, Raytheon requested that a series of cursory heat exchanger
tests be added. Raytheon supplied two similar aluminum heat exchangers identified by model
numbers C-002 and C-007. Both heat exchangers were designed with off-set aluminum strip
fins. Model C-002 contains 10 fins /inch (fpi) and model C-007, 24 fpi. Enclosure 10 shows the
test data and results used to generate the charts of Enclosures 7 and 8.
Enclosure 6 shows the R-134a test set-up and instrumentation. Inlet and outlet temperatures
were measured at T 8 and T 9 , respectively. Pressure and pressures drop values were measured
at P 2 and ΔP 1 , respectively. Flow rate values were taken from FM4. Two test series designed to
determine the thermal performance of the heat exchangers operating as evaporators and




                                                                                                3
condensers were performed.
Enclosure 7 is a sketch of the heat exchanger test configuration. It shows a distribution manifold
and off-set strip fin sandwiched between the top and bottom frames. Also shown on the frame
top are the R-134a inlet and exit and the location of the thermocouple holes. Directly above the
top and centered over the fins is a film heater (heat load). Covering the heater is a pad of
thermal insulation used to limit heat losses. Section A-A details the cross section and shows the
thermocouple holes and fin cavities.
Enclosures 8 and 9 summarize the test results for the evaporators and condensers,
respectively. The enclosures combine the thermal and flow resistance results into two charts for
the 10 fpi and 24 fpi heat exchangers. A cursory examination of the thermal resistances show
the 24 fpi heat exchanger values are lower than those of 10 fpi. Also, noted is the negligible
difference in flow resistance values between the two exchangers.

Enclosure 8, Chart 3 and Enclosure 9 Chart 5 summarize the thermal resistant results for the
exchangers tested as evaporators and condensers, respectively. Test results show that Model
C-007, 24fpi consistently has lower thermal resistance than Model C-002 10 fpi design. A
comparison of the evaporator data at an exit quality of 30% shows the 10 fpi value of 0.011 deg
C/W or 43% greater than the 0.006 deg C/W for the 24 fpi. Similarly, for the condenser at 30%
inlet quality, the 10 fpi heat exchanger resistance is 0.011 deg C/W or 50 % greater than the
0.005 deg C/W for the 24 fpi heat exchanger. Enclosure 8, Chart 4 and Enclosure 9, Chart 6
compare the flow resistance of each exchanger tested as evaporators and condensers,
respectively. Reviewing the charts shows little difference between both heat exchangers.
Maximum resistance value for the evaporator is 0.52 psid and occurs at an exit quality of 18%.
Correspondingly, the maximum condenser resistance is 1.4 psid at an inlet quality of 20 %.

Enclosure 10 tabulates the heat exchanges test data and results used in Enclosures 8 and 9.
Ten thermocouples located on the heat exchanges surface between the heater and the fins
(Enclosure 7) provide temperatures data. These values are averaged and subtracted from the
R-134a sink value (R-134a saturated discharge temperature). Note this value is T 9 for the
evaporator and T 8 for the condenser. Correspondingly, the vapor quality is determined from the
heat load, mass flow rate, and the vapor enthalpy. For example, Case no. 100 has an average
surface temperature of 30.4 ºC (Tave) and a saturation temperature of 27.9 ºC (Tsat) or a 2.9
deg C difference. The corresponding load is 203.7 W, thus, the thermal resistance for this case
is 0.0123 deg C/W. Determining the vapor quality requires converting 203.7 w to 695.2 Btuh,
changing the 5.0 gal/hr to an equivalent mass flow rate of 9.9 lb/hr (pph), and obtaining the
vapor enthalpy at 27.9 ºC. Enthalpy data taken from reference d shows a value of 75.9 Btuh/lb.
The vapor quality determined from these values is 0.183 or 18.3 %

Discussion of Results:
The PLMC technology is based on pumping 2 deg C sub-cooled R-134a refrigerant through a
heat exchanger (manifolds) where heat is transferred to the R-134a. The heat added to the R-
134a converts the sub-cooled liquid to a 32 ºC (90 ºF) isothermal mixture of saturated liquid and
vapor, typically known as a quality mixture. More specifically, quality is the weight ratio of the
vapor to the total weight of the mixture. As the mixture exits the heat exchanger it passes into a
long vertical tube called a separator. Here gravity causes the 32.0 ºC saturated liquid to collect
at the tube bottom displacing the vapor. The saturated liquid passes from the separator to a
mixing port upstream of the pump. The displaced vapor (32.0 ºC) passes through the condenser
and exits as a sub-cooled liquid at 28.0 ºC (4.0 deg C of sub-cooling). Combining the fluids at
the mixing port forms a 30.0 ºC sub-cooled liquid. Figure 2 of Enclosure 2 shows the 50%
quality mixture splitting into 41.1 lb/min (ppm) of saturated liquid collecting at the bottom of the



                                                                                                  4
separator and 41.1 ppm of vapor flowing to the condenser.

To prevent condensate from collecting on the external surfaces of the hardware, the R-134a
(coolant) is maintained above the local dew point temperature. A 30.0 ºC (86.0 ºF) value is
specified in the design criteria. A passive low cost OEM control required for maintaining the
coolant temperature also makes it possible to simply change the R-134a operating temperature.
Enclosure 5 addresses the sensitivity of the system to changes in cooling load. The PLMC
operating envelope for a design flow of 8.2 gpm and 30.0 ºC ranges from 109.6 kW to 37.3 kW.
However, the quality changes correspondingly from 25% to 75%. Potential changes to the
pump speed due to line voltage fluctuation or other minor aberrations have no effect on the
cooling performance of the system. However, any changes made in the heat load need to be
followed by changes in the condenser performance.
A specific request to measure the flow resistance of the fins only was made. Initial
measurements were inconclusive. Further investigation concluded that the measured values
were outside the resolution of the available test equipment. A default test that included the
manifold was adopted. Enclosure 8, Chart 4 and Enclosure 9, Chart 6 summarize the flow
resistance results for the heat exchangers. Both charts show that the 10 and 24 fpi flow
resistance values coincide. An explanation of this is found in the heat exchanger distribution
manifold design (Enclosure 7). The manifold governs the heat exchange flow resistance and is
designed with several times the resistance of the fins, thus, making the fin resistance values
insignificant.
The PLMC design results show that a R-134a EDA cooling system is a viable alternative to the
EGW platform. In summary, for the same design constraints as the EGW platform, the PLMC
delivers the same cooling performance at a lower coolant flow rate and subsequently lower
pressure drops. The package envelope and weight are considerably less. Parasitic power
requirement and hardware costs are lower.
Critical to the product development cycle is validating the design by building and testing a proof-
of-concept model. Therefore, it is recommended that a phase 2 SBIR proposal effort be
immediately addressed.
Conclusions:
The PLMC cooling technology provides a new and effective alternative to today’s conventional
design strategies. Visions of the PLMC technology beyond this study are major and complement
the technical challenges of the United States and the world. Adapting the PLMC cooling
technology into future U.S. defense projects will lower parasitic power demands, reduce
package envelope and weight, lower hardware costs, provide isothermal cooling, and widen
operating envelopes. These attributes support the philosophy of a lighter, faster, more effective
military at lower costs.

One major commercial contribution of the PLMC technology is in reducing the amount of waste
energy consumed by the world computer service industries. It is estimated that 40% of the
energy budgeted for cooling computers is used to maintain the computer room environments.
Most of this energy is used to power computer room fans and blowers to augment the cooling
process. By replacing the fans and blowers with the PLMC technology significantly reduce the
40% waste heat. TFF’s current model mounts cold plates to temperature sensitive components.
Manifolds within the cabinet distribute and collect the R-134a coolant. Heat generated by the
component isothermally changes the R-134a from a liquid to a vapor. Conversely, as the vapor
flows through the condenser, heat is transferred to the cooling media (water or air) converting
the vapor back to a liquid. By placing the condenser external to the building, the heat is




                                                                                                 5
transferred outside, thus, eliminating a significant amount of the fan and blower power
requirements.
Other commercialized avenues targeted for PLMC technology include laser technology, power
and power supplies, astronomy, medicine, and transportation.




                                                                                       6
Enclosure 1



                           SUMMARY OF RESULTS




      Reference Items              Design Constraints        System Design      % Change
                                      (Raytheon)                 (TFF)
System Performance
  Cooling Media                     Single Phase EGW 2     Two Phase R-134a
  Quality (%)                                 NA                  50              NA
  Heat Load (kw)                             54.4                54.4             NA
  Flow Rate (gpm)                            50.0                 8.2             -84
  Coolant Temperature ( C )                  30.0                30.0              0
  Max. Pressure (psig)                      125.0               112.3             -10
  Pressure Drops (psid)                     105.0                9.4              -91
EDA Manifold
  Load (kw)                                   6.8                   6.8           NA
  Coolant Temp ( C )                    30 in / 35 out        32 in / 32 out      NA
  Flow Rate (gpm)                             6.3                   1.0           -84
  Critical Temperatures ( C )                38.0                  34.0           NA
   Pressure Drops (psid)                    100.0                   8.9           -91
Heat Exchanger3
  Type                                      EGW                  Vapor            NA
  Size (Tons)                                15.5                 15.5            NA
  Flow Rate (gpm)                            50.0                 50.0            NA
  Supply Pressure (psig)                     20.0                 20.0            NA
  Supply Temperature ( C )                   15.0                 15.0            NA
Pump (centrifugal)
  HP                                         10.0                  0.2            -98
  Wt (Lb)                                   300.0                 25.0            -92
  Envelope (in)                             TBD              26quot; x 16quot; x 10quot;      TBD
System Impact
  Leakage1                        Contamination Potenial          None             NA
  Hardware Reliability (khrs)              No Data                 50             TBD
  Size                              60quot;L x 30quot;W x 60quot;H     25quot;L x 15quot;W x 45quot;H     -84
  Weight (Lb)                               874.0                 150.0           -83
  Power (kw)                                 7.5                   0.1            -98
  Hardware                              $11,340.00             ~ $6500.00         -43
1. Impact on leakage on electrical circuits
2. Single Phase EGW (55/45 by Vol)
  3. Water Cooled Heat Exchanger



                                                                                              7
Enclosure 2


COOLING CYCLE FLOW DIAGRAMS




                               8
Enclosure 3



                                                           SYSTEM FLOW SUMMARY



                            20.0
                                                                                                                         Notes:
                                                                                                                         1. Manufacturer….DTE Energy Technologies
                                                                  PREFERRED OPERATING RANGE                              2. Model ………..…HY-SAVE Model # 820 HYS
                                                                                                                         3. Part Number…...820-00-HYS
                                                                                                                         4. RPM…………….3550
                            16.0                                                                                         5. Fluid…………….R-134a
                                                                                                                         5. Tsat………….… 30 C (86 F)
                                                              Pump                                                       6. Quality ………… 50%
Pressure Drop (dP) / psid




                                                           Performance                                                     EDA Design
                                                                                                                            (R-134a)
                            12.0


                                         9.4                                                                  DP

                             8.0                                                     Metering Orifice
                                                                                       (6.4 psid)
                                                                                                                                                EDA Baseline
                                                                                                                                                  ( R-134a)


                             4.0
                                         3.1


                                                                                                        8.2
                             0.0
                                   0.0         1.0   2.0   3.0     4.0   5.0   6.0           7.0        8.0        9.0       10.0       11.0   12.0      13.0       14.0

                                                                         Volumetric Flow rate (V) /gpm




                                                                                                                                                          9
Enclosure 4




                                                                           FLOW RESISTANCE

                                    Chart1: System Flow Resistance
                            100.0
                                        Notes:
                                        1. Coolant…………………..R   -134a
                                        2. Coolant Tem ( C )…………..30
                                                      p                                                E Design
                                                                                                        DA
                                                                                                       Metering Orifices
Pressure Loss (dP) / pisd




                             10.0                               9.4                                    E Baseline
                                                                                                        DA
                                                                6.3


                                                                3.1




                              1.0




                                                                                        8.2

                              0.1
                                    1                                                           10                                          100

                                                                                    Flow Rate (V) / gpm


                                        Chart 2: EDA Baseline Flow Resistance
                            1000.0
                                            Notes:
                                            1. Coolant Temp ( C )………..30
Pressure Loss (dP) / pisd




                             100.0                                                                                   105




                                                                                                                      EGW Baseline
                              10.0                                                   R-134a Baseline




                                                                              3.1


                                                                                                                                     50
                                                                                          8.2
                                1.0
                                        1                                                        10                                          100

                                                                                    Flow Rate (V) / gpm
                                                                                                                                            10
Enclosure 5


                                                     LOAD SENSITIVITY



                160
                          Notes:
                          Coolant…………..R-134a
                140       Tsat ……………...30 C (86 F)
                          Flow ……………..8.2 gal/min

                120                                        PREFERRED OPERATING RANGE
                            109.6
Load (P) / kw




                100


                80


                60
                           54.4
                                                                               Design Goal
                40         37.3


                20


                 0
                      0             10         20     30        40        50           60    70   80           90

                                                           Design Quality (X) / %




                                                                                                          11
Enclosure 6



TEST FIXTURE AND INSTRUMENTATION




                                     12
Enclosure 7



                                HEAT EXCHANGER


                                                                             A
                                          0.38”T x 2“W x 4”L
                                          Thermal Insulation


                                                                                          2”x4” Film Heater (Load)
        Inlet                   Thermocouple Locations 10 plc’s)                           Exit




Distribution                            0.10”Tx2.0” W x4.0” L
Manifold                                  Off-Set Strip Fine




                                                                         A

    0.84”Tx 4.0”W x11.75” L Aluminum
    Heat Exchanger Frame (Bottom)

   0.84”Tx 4.0”W x11.75” L Aluminum
   Heat Exchanger Frame (Top)




                                                      Thermocouple Holes Locations (10)


                                                        0.05”Tx2” W x11.0”L
                                                       Off-Set Fin Cavity (Top)
                0.10”Tx2.0” W x4.0” L
                  Off-Set Strip Fine
                                                          0.05”Tx2” W x11.0” L
                                                       Off-Set Fin Cavity (Bottom)




                  Section A-A




                                                                                                                     13
Enclosure 8



                                                                       EVAPORATOR TEST RESULTS


                                                             Chart 3: Thermal Resistance
                                         0.014

                                         0.013
Thermal Resistance / deg C-wt -1




                                         0.012

                                         0.011                                                     10 fins/inch (C-002)

                                         0.010

                                         0.009

                                         0.008
                                                                                                         24 fins/inch (C-007)
                                         0.007

                                         0.006

                                         0.005

                                         0.004
                                                         0        10     20     30         40         50             60         70   80       90     100
                                                                                                Exit Quality (%)

                                                              Chart 4: Flow Restance
                                                      1.00
                               Pressure Loss / psid




                                                                                                       24 fin/inch
                                                                                 10 fins/inch



                                                                                                    10 fins / inch                    24 fins/inch
                                                      0.10




                                                                                                                     -



                                                      0.01                       -
                                                             10                                                                                            100
                                                                                                Exit Quality (X) / %




                                                                                                                                                       14
Enclosure 9



                                                                            CONDENSER TEST RESULTS

                                                                 Chart 5: Thermal Resistance
                                                         0.014

                                                         0.013
                       Thermal Resistance / deg C-W -1




                                                         0.012
                                                                                                                       10 fins/inch (C-002)
                                                         0.011

                                                          0.01

                                                         0.009

                                                         0.008

                                                         0.007

                                                         0.006
                                                                                                                     24 fins/inch (C-007)
                                                         0.005

                                                         0.004
                                                                 0         20          40             60               80                   100   120
                                                                                               Inlet Quality (%)



                                                          Chart 6: Flow Resistance
                            10.0
Pressure Drop / psid




                                                                                                             24 fins/inch
                                        1.0
                                                                                       10 fins/inch




                                        0.1
                                                         10                                           Inlet Quality (%)                                  100
                                                                                                                                                        15
Enclosure 10



        HEAT EXCHANGER TEST DATA AND RESULTS
Heat Exchanger ID

Fins/Inch                                    10                                                   24
PN                                    49956-H335240-1                                      49956-H335240-1
MFG                                        1TL57                                                1TL57
SERNO                                      C-002                                                C-007

Evaporator

          Case No            100     101     102          103     104     105     112     113     114          115     116     117
        FINS/INCH                                    10                                                   24
Temperatures
    CldPlt 1       (C)       28.7    28.6    28.9         29.2    29.1    29.8    28.6    28.6    28.7         28.9    29.3    30.1
    CldPlt 2       (C)       30.7    30.4    30.7         31.1    31.1    31.9    29.8    29.5    29.6         30.0    30.7    31.8
    CldPlt 3       (C)       31.3    31.1    31.3         32.3    32.5    33.3    31.1    30.9    31.1         31.9    32.9    34.0
    CldPlt 4       (C)       31.2    30.9    31.3         32.5    32.9    33.6    30.2    29.9    30.0         30.7    31.9    33.1
    CldPlt 5       (C)       29.6    29.4    29.6         30.7    31.0    31.7    28.9    28.6    28.6         29.0    29.7    30.7
   CldPlt 6        (C)       29.1    28.9    29.2         29.5    29.3    29.8    28.3    28.2    28.2         28.4    28.6    29.4
   CldPlt 7       (C)        30.9    30.5    30.7         31.2    31.0    31.6    30.2    29.8    29.7         30.0    30.4    31.3
   CldPlt 8       (C)        32.7    32.4    32.7         33.7    33.8    34.4    30.6    30.2    30.2         30.7    31.4    32.5
   CldPlt 9       (C)        30.7    30.4    30.5         31.6    31.9    32.7    29.6    29.3    29.2         29.5    30.3    31.6
   CldPlt 10      (C)        29.3    29.0    29.2         30.0    30.3    31.0    28.7    28.3    28.3         28.4    28.8    29.7
      T8          (C)        27.2    27.4    27.7         28.1    27.9    28.4    27.0    27.5    27.6         28.0    28.1    29.0
      T9           (C)       27.9    27.9    28.2         29.1    29.2    29.7    28.1    27.9    28.1         28.2    28.6    29.4
Sensors
       V1         (gph)       5.0     4.0     3.0          2.0     1.5     1.0     5.0     4.0     3.0          2.0     1.5     1.0
       P2           (psia)   103.7   103.1   104.1        104.4   103.0   103.4   103.9   103.4   103.4        103.6   103.3   102.9
      dP1           (psid)   0.497   0.356   0.222        0.098   0.048   0.011   0.519   0.361   0.223        0.104   0.043   0.010
Results
     Tave            (C)      30.4  30.2   30.4   31.2   31.3   32.0   29.6   29.3   29.4   29.8   30.4   31.4
      Tsat           (C)      27.9  27.9   28.2   29.1   29.2   29.7   28.1   27.9   28.1   28.2   28.6   29.4
     Load            (w)     203.7 203.7 203.7 203.7 203.7 203.7 204.6 204.6 204.6 204.6 204.6 204.6
        R         (deg C/w) 0.0123 0.0112 0.0106 0.0102 0.0104 0.0110 0.0075 0.0072 0.0063 0.0076 0.0089 0.0102
 Exit Quality        (%)      18.3  22.9   30.5   45.8   60.8   91.4   18.4   22.9   30.6   45.9   61.2   91.7



Condenser

   Case No.                  118     119     120          121     122     123     130     131     132          133     134     135
  FINS/INCH                                          24
Temperatures
    CldPlt 1        (C)      26.9    26.7    26.8         26.8    26.8    26.9    26.0    25.8    25.8         25.8    25.7    25.8
    CldPlt 2        (C)      26.9    26.8    26.9         26.8    26.7    26.8    25.4    25.3    25.5         25.5    25.3    25.4
    CldPlt 3        (C)      27.2    27.1    27.1         27.0    27.0    27.0    26.1    26.0    26.2         26.2    26.1    26.2
    CldPlt 4        (C)      27.3    27.2    27.2         27.1    27.1    27.1    27.3    27.2    27.4         27.4    27.3    27.3
    CldPlt 5        (C)      27.4    27.2    27.2         27.1    27.1    27.1    26.8    26.7    26.9         26.8    26.6    26.7
   CldPlt 6         (C)      25.9    25.7    25.8         25.8    25.8    25.9    24.7    24.5    24.7         24.8    24.7    24.8
   CldPlt 7         (C)      25.8    25.6    25.8         25.8    25.8    25.8    23.8    23.8    23.9         24.0    23.8    23.9
   CldPlt 8         (C)      26.8    26.7    26.7         26.7    26.6    26.7    24.8    24.8    24.9         25.0    24.9    24.9
   CldPlt 9         (C)      27.1    26.9    27.0         26.9    26.8    26.9    25.9    25.8    26.0         26.0    25.9    26.0
   CldPlt 10        (C)      27.3    27.2    27.2         27.1    27.0    27.1    26.6    26.5    26.6         26.6    26.4    26.5
      T8            (C)      28.0    27.8    27.9         27.7    27.7    27.7    28.2    28.0    28.1         28.0    27.9    27.9
      T9            (C)      27.9    27.7    27.8         27.6    27.6    27.6    28.1    27.9    28.0         27.9    27.8    27.9
Sensors
       V1           (gph)     5.0     4.0     3.0          2.0     1.5     1.0     5.0     4.0     3.0          2.0     1.5     1.0
       P1           (psia)   104.1   103.6   103.6        103.3   103.2   103.3   104.1   103.7   103.3        103.1   102.8   103.3
      dP1           (psid)   1.38    1.17    0.98         0.77    0.69    0.61    1.33    1.16    0.97         0.76    0.70    0.63
Results
      Tave           ( C)      26.8  26.7   26.8   26.7   26.7   26.7   25.7   25.6   25.8   25.8   25.7   25.8
      Tsat           ( C)      28.0  27.8   27.9   27.7   27.7   27.7   28.1   28.0   28.1   28.0   27.9   27.9
      Load           (wt)     207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1
        R         (deg C/wt) 0.0058 0.0054 0.0053 0.0050 0.0050 0.0050 0.0115 0.0115 0.0114 0.0106 0.0106 0.0105
  Inlet Quality      (%)       20.4  25.5   33.9   50.9   67.8 101.7 20.4      25.5   33.9   50.8   67.7 101.7




                                                                                                                                         16
Enclosure 11




                                PUMP RELIABILITY

                                     Hy-Save Energy
                                Conservation Technologies
                                        PO Box 631
                                     4701 Ridge Road
                                   Cazenovia NY 13035
                            Phone 315 655 3322 Fax 315 655 4539
                                E-mail hysaveect@aol.com

August 23, 2001

To: Joe Marsala

From: Walter Joncas

Subject: Refrigerant pump reliability


I will attempt to keep this short and to the point.

After Studies conducted by the National Institute of Standards and Technology (NIST) were
completed and a public report filed The Federal Energy Management Program (FEMP) published
its report in 1995 on the Hy-Save Pump. On the first page of the FEMP report it states that the
Hy-Save Pump was “ultra reliable”. That finding is a result of The US Governments, Pacific
Northwest Laboratory, Richland Washington study of the Hy-Save Pump over a two-year period.

In support of that study an audit of all repair parts sold by Hy-Save for any reason was conducted.
At that point in time 12,500 refrigerant pumps had been installed primarily in refrigeration
systems. Sixty million operating hours is estimated based on 10,000 of the pumps operating at
least 6000 hours per year in a full time refrigeration environment.
A total of 124 impeller / shaft replacements were made during this same time period. Of the 124
impeller / shaft sets replaced, 60 were replaced as a result R&D testing of materials. Forty three
of the Impeller / shaft assemblies were damaged by running dry due to improper piping practice
and or loss of refrigerant through a leak elsewhere in the host system. This caused the bearings to
overheat thus causing failure. The remaining 21 sets showed signs of bearing material
breakdown. At least 10 of those were due to contamination within the system. There were 11
failures of unknown origin. No (of what could be considered normal), worn out impeller bearings
or shafts causing failure were observed.

On a more localized basis, and specific to the pump you are using, the east coast suppliers
(Cazenovia, New York, Gainesville, Florida) have not shipped any replacement parts for the
model 809IND for any reason to any point east of the Mississippi in the past four years with one
exception. The exception is Thermal Form and Function, Manchester MA. Spare parts have been
shipped and inventoried at their location but those parts have not been used. I could not confirm
what was shipped west of the Mississippi in exact terms during this same time period. However I
have strong reason to believe the number was less than three.




                                                                                                      17

Contenu connexe

Tendances

Design and Development of Cascade Refrigeration System
Design  and Development of Cascade Refrigeration SystemDesign  and Development of Cascade Refrigeration System
Design and Development of Cascade Refrigeration SystemIRJET Journal
 
Zeus superior k w export manual tehnic - st-zkw ed 12-07 (en)
Zeus superior k w export   manual tehnic - st-zkw ed 12-07 (en)Zeus superior k w export   manual tehnic - st-zkw ed 12-07 (en)
Zeus superior k w export manual tehnic - st-zkw ed 12-07 (en)Costel Sirghi
 
Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...ijics
 
Affinity Laws for Variable Speed Centrifugal Pumps
Affinity Laws for Variable Speed Centrifugal PumpsAffinity Laws for Variable Speed Centrifugal Pumps
Affinity Laws for Variable Speed Centrifugal PumpsVijay Sarathy
 
Surge Control for Parallel Centrifugal Compressor Operations
Surge Control for Parallel Centrifugal Compressor OperationsSurge Control for Parallel Centrifugal Compressor Operations
Surge Control for Parallel Centrifugal Compressor OperationsVijay Sarathy
 
Introduction to Boiler Control Systems
Introduction to Boiler Control SystemsIntroduction to Boiler Control Systems
Introduction to Boiler Control Systemsno suhaila
 
Boiler
BoilerBoiler
Boileravik
 
Adding new elements in old Control Loops
Adding new elements in old Control LoopsAdding new elements in old Control Loops
Adding new elements in old Control LoopsMusharif Hussain
 
ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...
ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...
ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...Vijay Sarathy
 
Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...
Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...
Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...Centro Studi Galileo
 
INSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROL
INSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROLINSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROL
INSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROLno suhaila
 
Practical Boiler Control and Instrumentation for Engineers and Technicians
Practical Boiler Control and Instrumentation for Engineers and TechniciansPractical Boiler Control and Instrumentation for Engineers and Technicians
Practical Boiler Control and Instrumentation for Engineers and TechniciansLiving Online
 
Simulation of thermodynamic analysis of cascade refrigeration system with alt...
Simulation of thermodynamic analysis of cascade refrigeration system with alt...Simulation of thermodynamic analysis of cascade refrigeration system with alt...
Simulation of thermodynamic analysis of cascade refrigeration system with alt...IAEME Publication
 
Instrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power PlantInstrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power PlantSHIVAJI CHOUDHURY
 
MODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICS
MODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICSMODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICS
MODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICSVijay Sarathy
 

Tendances (19)

Design and Development of Cascade Refrigeration System
Design  and Development of Cascade Refrigeration SystemDesign  and Development of Cascade Refrigeration System
Design and Development of Cascade Refrigeration System
 
Zeus superior k w export manual tehnic - st-zkw ed 12-07 (en)
Zeus superior k w export   manual tehnic - st-zkw ed 12-07 (en)Zeus superior k w export   manual tehnic - st-zkw ed 12-07 (en)
Zeus superior k w export manual tehnic - st-zkw ed 12-07 (en)
 
Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...Importance of three elements boiler drum level control and its installation i...
Importance of three elements boiler drum level control and its installation i...
 
Affinity Laws for Variable Speed Centrifugal Pumps
Affinity Laws for Variable Speed Centrifugal PumpsAffinity Laws for Variable Speed Centrifugal Pumps
Affinity Laws for Variable Speed Centrifugal Pumps
 
Drun level control
Drun level controlDrun level control
Drun level control
 
Surge Control for Parallel Centrifugal Compressor Operations
Surge Control for Parallel Centrifugal Compressor OperationsSurge Control for Parallel Centrifugal Compressor Operations
Surge Control for Parallel Centrifugal Compressor Operations
 
Introduction to Boiler Control Systems
Introduction to Boiler Control SystemsIntroduction to Boiler Control Systems
Introduction to Boiler Control Systems
 
Boiler
BoilerBoiler
Boiler
 
S130304109117
S130304109117S130304109117
S130304109117
 
Adding new elements in old Control Loops
Adding new elements in old Control LoopsAdding new elements in old Control Loops
Adding new elements in old Control Loops
 
ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...
ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...
ASPEN HYSYS DYNAMICS MODELLING OF DIFFERENTIAL PRESSURE (DP) TRANSMITTER FOR ...
 
Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...
Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...
Joachim Gerstel - DuPont - NUOVI REFRIGERANTI A BASSO GWP ALTERNATIVI ALL’R-4...
 
INSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROL
INSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROLINSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROL
INSTRUMENTATION AND PROCESS CONTROL - BOILER CONTROL
 
Practical Boiler Control and Instrumentation for Engineers and Technicians
Practical Boiler Control and Instrumentation for Engineers and TechniciansPractical Boiler Control and Instrumentation for Engineers and Technicians
Practical Boiler Control and Instrumentation for Engineers and Technicians
 
Simulation of thermodynamic analysis of cascade refrigeration system with alt...
Simulation of thermodynamic analysis of cascade refrigeration system with alt...Simulation of thermodynamic analysis of cascade refrigeration system with alt...
Simulation of thermodynamic analysis of cascade refrigeration system with alt...
 
Instrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power PlantInstrumentation & Control For Thermal Power Plant
Instrumentation & Control For Thermal Power Plant
 
MODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICS
MODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICSMODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICS
MODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN ASPEN HYSYS DYNAMICS
 
Drum level
Drum levelDrum level
Drum level
 
Combustion control
Combustion controlCombustion control
Combustion control
 

En vedette

Beautiful flowers
Beautiful flowersBeautiful flowers
Beautiful flowersSylvi O.
 
Indirect Channel Recruitment
Indirect Channel RecruitmentIndirect Channel Recruitment
Indirect Channel RecruitmentRelayware, Inc.
 
Emberi Kapcsolatok
Emberi KapcsolatokEmberi Kapcsolatok
Emberi KapcsolatokSylvi O.
 
Best of National Geographic
Best of National GeographicBest of National Geographic
Best of National GeographicSylvi O.
 
Heartbreaker
HeartbreakerHeartbreaker
HeartbreakerSylvi O.
 
Szabadság
SzabadságSzabadság
SzabadságSylvi O.
 
Kék Madár
Kék MadárKék Madár
Kék MadárSylvi O.
 
Motivationsposter
MotivationsposterMotivationsposter
MotivationsposterSylvi O.
 
This is love.../ Das ist Liebe...
This is love.../ Das ist Liebe...This is love.../ Das ist Liebe...
This is love.../ Das ist Liebe...Sylvi O.
 
Channel Ecosystem Collaboration and the Case for Purpose-Built Technology
Channel Ecosystem Collaboration and the Case for Purpose-Built TechnologyChannel Ecosystem Collaboration and the Case for Purpose-Built Technology
Channel Ecosystem Collaboration and the Case for Purpose-Built TechnologyRelayware, Inc.
 
Kitchen Art
Kitchen ArtKitchen Art
Kitchen ArtSylvi O.
 
Enni vagy Nem Enni ?
Enni  vagy Nem Enni ?Enni  vagy Nem Enni ?
Enni vagy Nem Enni ?Sylvi O.
 
Lourdes felé...
Lourdes felé...Lourdes felé...
Lourdes felé...Sylvi O.
 
Kittens,Katzen, Kiscicák
Kittens,Katzen, KiscicákKittens,Katzen, Kiscicák
Kittens,Katzen, KiscicákSylvi O.
 
Moments de reflexion
Moments de reflexionMoments de reflexion
Moments de reflexionSylvi O.
 

En vedette (20)

Beautiful flowers
Beautiful flowersBeautiful flowers
Beautiful flowers
 
Videre Corporate 10 21 08
Videre Corporate 10 21 08Videre Corporate 10 21 08
Videre Corporate 10 21 08
 
Indirect Channel Recruitment
Indirect Channel RecruitmentIndirect Channel Recruitment
Indirect Channel Recruitment
 
Szőkék
SzőkékSzőkék
Szőkék
 
Emberi Kapcsolatok
Emberi KapcsolatokEmberi Kapcsolatok
Emberi Kapcsolatok
 
Best of National Geographic
Best of National GeographicBest of National Geographic
Best of National Geographic
 
Heartbreaker
HeartbreakerHeartbreaker
Heartbreaker
 
Szabadság
SzabadságSzabadság
Szabadság
 
Kék Madár
Kék MadárKék Madár
Kék Madár
 
Motivationsposter
MotivationsposterMotivationsposter
Motivationsposter
 
PUP SI PUP NO
PUP SI PUP NOPUP SI PUP NO
PUP SI PUP NO
 
This is love.../ Das ist Liebe...
This is love.../ Das ist Liebe...This is love.../ Das ist Liebe...
This is love.../ Das ist Liebe...
 
Channel Ecosystem Collaboration and the Case for Purpose-Built Technology
Channel Ecosystem Collaboration and the Case for Purpose-Built TechnologyChannel Ecosystem Collaboration and the Case for Purpose-Built Technology
Channel Ecosystem Collaboration and the Case for Purpose-Built Technology
 
Partytime
PartytimePartytime
Partytime
 
Kitchen Art
Kitchen ArtKitchen Art
Kitchen Art
 
Enni vagy Nem Enni ?
Enni  vagy Nem Enni ?Enni  vagy Nem Enni ?
Enni vagy Nem Enni ?
 
Lourdes felé...
Lourdes felé...Lourdes felé...
Lourdes felé...
 
Kittens,Katzen, Kiscicák
Kittens,Katzen, KiscicákKittens,Katzen, Kiscicák
Kittens,Katzen, Kiscicák
 
Moments de reflexion
Moments de reflexionMoments de reflexion
Moments de reflexion
 
Rekviem
RekviemRekviem
Rekviem
 

Similaire à SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling

Calculation of Forces on Reactor Containment Fan Cooler Piping.pdf
Calculation of Forces on Reactor Containment Fan Cooler Piping.pdfCalculation of Forces on Reactor Containment Fan Cooler Piping.pdf
Calculation of Forces on Reactor Containment Fan Cooler Piping.pdfJoe Miller
 
SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...
SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...
SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...IAEME Publication
 
Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...
Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...
Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...IJMREMJournal
 
4 modeling and control of distillation column in a petroleum process
4 modeling and control of distillation column in a petroleum process4 modeling and control of distillation column in a petroleum process
4 modeling and control of distillation column in a petroleum processnazir1988
 
Pressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channelPressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channelIRJET Journal
 
1975Z-1-TBT-4150-0001-A1
1975Z-1-TBT-4150-0001-A11975Z-1-TBT-4150-0001-A1
1975Z-1-TBT-4150-0001-A1CangTo Cheah
 
Development of a Bench-Top Air-to-Water Heat Pump Experimental Apparatus
Development of a Bench-Top Air-to-Water Heat Pump Experimental ApparatusDevelopment of a Bench-Top Air-to-Water Heat Pump Experimental Apparatus
Development of a Bench-Top Air-to-Water Heat Pump Experimental ApparatusCSCJournals
 
Handbook of mechanical engineering calculations
Handbook of mechanical engineering calculationsHandbook of mechanical engineering calculations
Handbook of mechanical engineering calculationsRoddy Castro
 
R&ac lecture 25
R&ac lecture 25R&ac lecture 25
R&ac lecture 25sayed fathy
 
Bluon TdX 20 Compared to R-22 Testing Summary
Bluon TdX 20 Compared to R-22 Testing SummaryBluon TdX 20 Compared to R-22 Testing Summary
Bluon TdX 20 Compared to R-22 Testing SummaryBluon Energy
 
Best of breed control of platinum reactors
Best of breed control of platinum reactorsBest of breed control of platinum reactors
Best of breed control of platinum reactorsRotimi Agbebi
 
Cep plate and_frame_hx
Cep plate and_frame_hxCep plate and_frame_hx
Cep plate and_frame_hxHsien Yu Wang
 
Design plate heat exchangers
Design plate heat exchangersDesign plate heat exchangers
Design plate heat exchangersXuan Tung
 
Plate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger SizingPlate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger SizingSyed Waqas Haider
 
Simulation analysis of Series Cascade control Structure and anti-reset windup...
Simulation analysis of Series Cascade control Structure and anti-reset windup...Simulation analysis of Series Cascade control Structure and anti-reset windup...
Simulation analysis of Series Cascade control Structure and anti-reset windup...IOSR Journals
 
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptxNUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptxbatan5455
 
3 e analysis of thermal power plants
3 e analysis of thermal power plants3 e analysis of thermal power plants
3 e analysis of thermal power plantsGovind Kumar Mishra
 
Experimental investigate to obtain the effectiveness of regenerator using Air.
Experimental investigate to obtain the effectiveness of regenerator using Air.Experimental investigate to obtain the effectiveness of regenerator using Air.
Experimental investigate to obtain the effectiveness of regenerator using Air.IJESFT
 

Similaire à SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling (20)

Adm apn045-en 0912
Adm apn045-en 0912Adm apn045-en 0912
Adm apn045-en 0912
 
Calculation of Forces on Reactor Containment Fan Cooler Piping.pdf
Calculation of Forces on Reactor Containment Fan Cooler Piping.pdfCalculation of Forces on Reactor Containment Fan Cooler Piping.pdf
Calculation of Forces on Reactor Containment Fan Cooler Piping.pdf
 
SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...
SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...
SIMULATION OF THERMODYNAMIC ANALYSIS OF CASCADE REFRIGERATION SYSTEM WITH ALT...
 
Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...
Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...
Reactivity Feedback Effect on the Reactor Behaviour during SBLOCA in a 4-loop...
 
4 modeling and control of distillation column in a petroleum process
4 modeling and control of distillation column in a petroleum process4 modeling and control of distillation column in a petroleum process
4 modeling and control of distillation column in a petroleum process
 
Pressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channelPressure drop analysis of flow through pin fin channel
Pressure drop analysis of flow through pin fin channel
 
1975Z-1-TBT-4150-0001-A1
1975Z-1-TBT-4150-0001-A11975Z-1-TBT-4150-0001-A1
1975Z-1-TBT-4150-0001-A1
 
Development of a Bench-Top Air-to-Water Heat Pump Experimental Apparatus
Development of a Bench-Top Air-to-Water Heat Pump Experimental ApparatusDevelopment of a Bench-Top Air-to-Water Heat Pump Experimental Apparatus
Development of a Bench-Top Air-to-Water Heat Pump Experimental Apparatus
 
Handbook of mechanical engineering calculations
Handbook of mechanical engineering calculationsHandbook of mechanical engineering calculations
Handbook of mechanical engineering calculations
 
R&ac lecture 25
R&ac lecture 25R&ac lecture 25
R&ac lecture 25
 
Bluon TdX 20 Compared to R-22 Testing Summary
Bluon TdX 20 Compared to R-22 Testing SummaryBluon TdX 20 Compared to R-22 Testing Summary
Bluon TdX 20 Compared to R-22 Testing Summary
 
Best of breed control of platinum reactors
Best of breed control of platinum reactorsBest of breed control of platinum reactors
Best of breed control of platinum reactors
 
Final stage T2
Final stage T2Final stage T2
Final stage T2
 
Cep plate and_frame_hx
Cep plate and_frame_hxCep plate and_frame_hx
Cep plate and_frame_hx
 
Design plate heat exchangers
Design plate heat exchangersDesign plate heat exchangers
Design plate heat exchangers
 
Plate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger SizingPlate and frame Heat Exchanger Sizing
Plate and frame Heat Exchanger Sizing
 
Simulation analysis of Series Cascade control Structure and anti-reset windup...
Simulation analysis of Series Cascade control Structure and anti-reset windup...Simulation analysis of Series Cascade control Structure and anti-reset windup...
Simulation analysis of Series Cascade control Structure and anti-reset windup...
 
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptxNUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
NUCLEAR SAFETY CULTURE_dsa_sumantri.pptx
 
3 e analysis of thermal power plants
3 e analysis of thermal power plants3 e analysis of thermal power plants
3 e analysis of thermal power plants
 
Experimental investigate to obtain the effectiveness of regenerator using Air.
Experimental investigate to obtain the effectiveness of regenerator using Air.Experimental investigate to obtain the effectiveness of regenerator using Air.
Experimental investigate to obtain the effectiveness of regenerator using Air.
 

Plus de martyp01

PLRC Overview Rev2
PLRC Overview Rev2PLRC Overview Rev2
PLRC Overview Rev2martyp01
 
Chronological Senior Mechanical Packaging Engineer Resume1 1
Chronological Senior Mechanical Packaging Engineer Resume1 1Chronological Senior Mechanical Packaging Engineer Resume1 1
Chronological Senior Mechanical Packaging Engineer Resume1 1martyp01
 
Simplified Packaging Technique
Simplified Packaging TechniqueSimplified Packaging Technique
Simplified Packaging Techniquemartyp01
 
Effective Low Cost Alternative To Liquid Cooling
Effective Low Cost Alternative To Liquid CoolingEffective Low Cost Alternative To Liquid Cooling
Effective Low Cost Alternative To Liquid Coolingmartyp01
 
Thermal Design And Performance Of Two Phase Meso Scale Heat Exchanger
Thermal Design And Performance Of Two Phase Meso Scale Heat ExchangerThermal Design And Performance Of Two Phase Meso Scale Heat Exchanger
Thermal Design And Performance Of Two Phase Meso Scale Heat Exchangermartyp01
 
Enterprise High Desity Cooling
Enterprise High Desity CoolingEnterprise High Desity Cooling
Enterprise High Desity Coolingmartyp01
 

Plus de martyp01 (6)

PLRC Overview Rev2
PLRC Overview Rev2PLRC Overview Rev2
PLRC Overview Rev2
 
Chronological Senior Mechanical Packaging Engineer Resume1 1
Chronological Senior Mechanical Packaging Engineer Resume1 1Chronological Senior Mechanical Packaging Engineer Resume1 1
Chronological Senior Mechanical Packaging Engineer Resume1 1
 
Simplified Packaging Technique
Simplified Packaging TechniqueSimplified Packaging Technique
Simplified Packaging Technique
 
Effective Low Cost Alternative To Liquid Cooling
Effective Low Cost Alternative To Liquid CoolingEffective Low Cost Alternative To Liquid Cooling
Effective Low Cost Alternative To Liquid Cooling
 
Thermal Design And Performance Of Two Phase Meso Scale Heat Exchanger
Thermal Design And Performance Of Two Phase Meso Scale Heat ExchangerThermal Design And Performance Of Two Phase Meso Scale Heat Exchanger
Thermal Design And Performance Of Two Phase Meso Scale Heat Exchanger
 
Enterprise High Desity Cooling
Enterprise High Desity CoolingEnterprise High Desity Cooling
Enterprise High Desity Cooling
 

Dernier

Models of Disability - an overview by Marno Retief & Rantoa Letšosa
Models of Disability - an overview by Marno Retief & Rantoa LetšosaModels of Disability - an overview by Marno Retief & Rantoa Letšosa
Models of Disability - an overview by Marno Retief & Rantoa Letšosaannemarleenolthof1
 
Unlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdf
Unlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdfUnlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdf
Unlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdfIBM
 
Design mental models for managing large-scale dbt projects. March 21, 2024 in...
Design mental models for managing large-scale dbt projects. March 21, 2024 in...Design mental models for managing large-scale dbt projects. March 21, 2024 in...
Design mental models for managing large-scale dbt projects. March 21, 2024 in...Ed Orozco
 
Math Group 3 Presentation OLOLOLOLILOOLLOLOL
Math Group 3 Presentation OLOLOLOLILOOLLOLOLMath Group 3 Presentation OLOLOLOLILOOLLOLOL
Math Group 3 Presentation OLOLOLOLILOOLLOLOLkenzukiri
 
How to use Ai for UX UI Design | ChatGPT
How to use Ai for UX UI Design | ChatGPTHow to use Ai for UX UI Design | ChatGPT
How to use Ai for UX UI Design | ChatGPTThink 360 Studio
 
Embroidery design from embroidery magazine
Embroidery design from embroidery magazineEmbroidery design from embroidery magazine
Embroidery design from embroidery magazineRivanEleraki
 
The future of UX design support tools - talk Paris March 2024
The future of UX design support tools - talk Paris March 2024The future of UX design support tools - talk Paris March 2024
The future of UX design support tools - talk Paris March 2024Alan Dix
 
WCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptx
WCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptxWCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptx
WCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptxHasan S
 
Designing for privacy: 3 essential UX habits for product teams
Designing for privacy: 3 essential UX habits for product teamsDesigning for privacy: 3 essential UX habits for product teams
Designing for privacy: 3 essential UX habits for product teamsBlock Party
 
LRFD Bridge Design Specifications-AASHTO (2014).pdf
LRFD Bridge Design Specifications-AASHTO (2014).pdfLRFD Bridge Design Specifications-AASHTO (2014).pdf
LRFD Bridge Design Specifications-AASHTO (2014).pdfHctorFranciscoSnchez1
 
Construction Documents Checklist before Construction
Construction Documents Checklist before ConstructionConstruction Documents Checklist before Construction
Construction Documents Checklist before ConstructionResDraft
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara Rakovska
AMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara RakovskaAMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara Rakovska
AMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara RakovskaBarusRa
 
High-Quality Faux Embroidery Services | Cre8iveSkill
High-Quality Faux Embroidery Services | Cre8iveSkillHigh-Quality Faux Embroidery Services | Cre8iveSkill
High-Quality Faux Embroidery Services | Cre8iveSkillCre8iveskill
 
Create Funeral Invites Online @ feedvu.com
Create Funeral Invites Online @ feedvu.comCreate Funeral Invites Online @ feedvu.com
Create Funeral Invites Online @ feedvu.comjakyjhon00
 
UX Conference on UX Research Trends in 2024
UX Conference on UX Research Trends in 2024UX Conference on UX Research Trends in 2024
UX Conference on UX Research Trends in 2024mikailaoh
 
Khushi sharma undergraduate portfolio...
Khushi sharma undergraduate portfolio...Khushi sharma undergraduate portfolio...
Khushi sharma undergraduate portfolio...khushisharma298853
 
UI UX Process for SaaS Product Design Success
UI UX Process for SaaS Product Design SuccessUI UX Process for SaaS Product Design Success
UI UX Process for SaaS Product Design SuccessThink 360 Studio
 
Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024
Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024
Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024Ted Drake
 

Dernier (18)

Models of Disability - an overview by Marno Retief & Rantoa Letšosa
Models of Disability - an overview by Marno Retief & Rantoa LetšosaModels of Disability - an overview by Marno Retief & Rantoa Letšosa
Models of Disability - an overview by Marno Retief & Rantoa Letšosa
 
Unlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdf
Unlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdfUnlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdf
Unlocking Conversion_ The Art of Turning Visitors into Loyal Customers.pdf
 
Design mental models for managing large-scale dbt projects. March 21, 2024 in...
Design mental models for managing large-scale dbt projects. March 21, 2024 in...Design mental models for managing large-scale dbt projects. March 21, 2024 in...
Design mental models for managing large-scale dbt projects. March 21, 2024 in...
 
Math Group 3 Presentation OLOLOLOLILOOLLOLOL
Math Group 3 Presentation OLOLOLOLILOOLLOLOLMath Group 3 Presentation OLOLOLOLILOOLLOLOL
Math Group 3 Presentation OLOLOLOLILOOLLOLOL
 
How to use Ai for UX UI Design | ChatGPT
How to use Ai for UX UI Design | ChatGPTHow to use Ai for UX UI Design | ChatGPT
How to use Ai for UX UI Design | ChatGPT
 
Embroidery design from embroidery magazine
Embroidery design from embroidery magazineEmbroidery design from embroidery magazine
Embroidery design from embroidery magazine
 
The future of UX design support tools - talk Paris March 2024
The future of UX design support tools - talk Paris March 2024The future of UX design support tools - talk Paris March 2024
The future of UX design support tools - talk Paris March 2024
 
WCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptx
WCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptxWCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptx
WCM Branding Agency | 210519 - Portfolio Review (F&B) -s.pptx
 
Designing for privacy: 3 essential UX habits for product teams
Designing for privacy: 3 essential UX habits for product teamsDesigning for privacy: 3 essential UX habits for product teams
Designing for privacy: 3 essential UX habits for product teams
 
LRFD Bridge Design Specifications-AASHTO (2014).pdf
LRFD Bridge Design Specifications-AASHTO (2014).pdfLRFD Bridge Design Specifications-AASHTO (2014).pdf
LRFD Bridge Design Specifications-AASHTO (2014).pdf
 
Construction Documents Checklist before Construction
Construction Documents Checklist before ConstructionConstruction Documents Checklist before Construction
Construction Documents Checklist before Construction
 
AMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara Rakovska
AMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara RakovskaAMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara Rakovska
AMBER GRAIN EMBROIDERY | Growing folklore elements | Barbara Rakovska
 
High-Quality Faux Embroidery Services | Cre8iveSkill
High-Quality Faux Embroidery Services | Cre8iveSkillHigh-Quality Faux Embroidery Services | Cre8iveSkill
High-Quality Faux Embroidery Services | Cre8iveSkill
 
Create Funeral Invites Online @ feedvu.com
Create Funeral Invites Online @ feedvu.comCreate Funeral Invites Online @ feedvu.com
Create Funeral Invites Online @ feedvu.com
 
UX Conference on UX Research Trends in 2024
UX Conference on UX Research Trends in 2024UX Conference on UX Research Trends in 2024
UX Conference on UX Research Trends in 2024
 
Khushi sharma undergraduate portfolio...
Khushi sharma undergraduate portfolio...Khushi sharma undergraduate portfolio...
Khushi sharma undergraduate portfolio...
 
UI UX Process for SaaS Product Design Success
UI UX Process for SaaS Product Design SuccessUI UX Process for SaaS Product Design Success
UI UX Process for SaaS Product Design Success
 
Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024
Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024
Introduce Trauma-Informed Design to Your Organization - CSUN ATC 2024
 

SBIR, Low Cost High Performance State-of-the Art Phased Array Radar Cooling

  • 1. To: Wayne Liang Principle Investigator: Martin Pitasi Submission Date: 21AUG04 Title: Ballistic Missile Innovative Radar and RF Products Subtitle: Phase 1 Final Report References: a. SBIR Topic No. MDA03-052 b. Proposal Number B031-1925 c. Contract No. N00178-04-C-3046 d. Page 7 of the Technical Information Document, No. R-134a, titled “Thermodynamic Properties of HFC-134a,” published by Dupont SUVA Enclosures: 1. Summary of Results 2. Cooling Cycle Flow Diagrams0 3. System Flow Summary 4. Flow Resistance 5. Load Sensitivity 6. Test Fixture and Instrumentation 7. Heat Exchanger 8. Evaporator Test Results 9. Condenser Test Results 10. Heat Exchanger Test Data and Results 11. Pump Reliability Summary: The goal of this Phase 1 SBIR study is to demonstrate to the Missile Defense Agency (MDA) that pumped liquid multi-phase cooling (PLMC) technology offers a superior and credible alternative to conventional single-phase ethylene glycol/water (EGW) systems. The results show conclusively that a PLMC system designed as a potential replacement for the EGW system performs equally well. Primary advantages of the PLMC design are its inherent isothermal cooling, higher reliability, lower hardware and operating costs, smaller package envelope, and reduced weight. Background: To enhance and augment Phase Array Radar performance, Raytheon requested (Reference a) that Thermal Form and Function (TFF) submit a proposal to the MDA SBIR program (Reference b). As a result of this effort, TFF was awarded a Phase 1 contract (Reference c) to compare the cooling performances of an existing EGW phase-array cooling platform to a similar PLMC design. In support of the study, design criteria data was leveraged from an existing Raytheon EGW cooling platform (Enclosure 1). PLMC technology was developed in 1998 by Thermal Form & Function for cooling Compaq Computer’s Alpha Server Division, next-generation, Enterprise Servers. The technology was driven by design constraints beyond the limits of conventional cooling capabilities. Constraints included maintaining 32, 200 W computer processor packages at operating junction temperatures below 85 ºC, reliability and safety, package size and weight, and hardware and operating cost limits. From these constraints, pumped liquid multi-phase cooling (PLMC) evolved. The PLMC design consists of commercially available hardware that includes a 1
  • 2. refrigerant pump, air- and water-cooled condensers, distribution manifold, separator, reservoir, and system controls. To demonstrate the technology a proof-of-concept system packaged in a standard 18” cabinet was built and tested. The test data and accompanying results confirmed that the PLMC system met all the design constraints defined by Compaq Computer. Since 1998, the technology roadmap has successfully evolved from cabinet cooling to rack, 1U, and blade designs. Results: The summary of the results is shown in Enclosure 1. Listed are Raytheon’s EGW design constraint values and corresponding reference items. Adjacent to these values are Thermal Form and Function’s PLMC R-134a system design results. Both values are compared and shown as a percentage change. At a heat load of 54.4 kW and a coolant temperature of 30.0 ºC (86.0 ºF), the PLMC design requires 8.2 gal/min (gpm) of R-134a coolant. This value is 84% lower than the 50 gpm specified for the EGW platform. Subsequent reductions of 91% and 98 % are reflected in the system pressure drop and pump horsepower, respectively. Correspondingly, similar changes in flow and pressure drop are reflected in the EDA manifold section. The critical manifold temperature for the PLMC design is 34 ºC or 12 % lower the 38 ºC EGW value. Chilled water provided for cooling the EGW heat exchanger or PLMC condenser will deliver 50 gpm of water at 15.0 ºC (59.0 ºF) and 20.0 psig. The R-134a pump advantages include a reduction in horsepower and weight requirements. Horsepower requirements drop from 10, for the EGW pump, to 0.2 for the R-134a pump or 98%. Correspondingly, the weight change is from 300lb to 25lb or 92% lower. The potential of electronics failing due to liquid leakage associated with the ethylene glycol/water cooling system exists and needs to be considered as having a negative impact on reliability. However, any R-134a leaks occur in the form of a non-toxic, non-ozone depleting, inert vapor that has no detrimental effect on electronics. Refrigerant pump hardware reliability is listed as high and is based on 11 failures of unknown origin over 60 million pump hours of operation (Enclosure 11). No reliability data exist for the EGW pump. Estimated package volumes for the PLMC design and the EGW platform are16, 875 in3 (25”L x 15”W x 45”H) and 108,000 in3 (60”L x 30”W x 60”H), respectively. Comparing these results shows that the PLMC design envelope is 84% smaller than the Raytheon platform. Correspondingly, the PLMC system weight of 150 lb is 83% lighter than the 874 lb Raytheon platform. This study assumes that the pumps consume 100 % of the parasitic power. Instrument and control power is considered negligible and have no impact on the results. Pump specification indicate that the R-134a pump uses 0.12 kW or 98 % less power than the 7.5 kW needed by the EGW pump. Hardware costs figures for the Raytheon platform and the PLMC design are $11,340 and $6500, respectively, or 43% less. Enclosure 2 details the flow diagrams for the EGW platform and PLMC system design. Figures 1 and 2 show the Raytheon design criteria and PLMC design results, respectively. The EGW diagram (Figure 1) shows 50 gpm of ethylene glycol/water pumped at 35.0 ºC (95.0 ºF) and 125.0 psig though a water-cooled heat exchanger. The heat exchanger removes 54.4 kW and 2
  • 3. reduces the coolant temperature from 35.0 ºC (95.0 ºF) to 30.0 ºC (86.0 ºF). The coolant flows into the EDA assembly and is uniformly distributed between the manifolds. Approximately 6.3 gpm of coolant passes through each manifold cooling 6.8 kW of EDA power, raising the fluid temperature from 30.0 ºC to 35.0 ºC. The coolant exits the EDA at 35.0 ºC and 5.0 psig then flows through the filter prior to entering the pump. Filter and miscellaneous line losses account for the remaining 5 psig. A reservoir located prior to the filter provides a controlled volume designed to compensate for any coolant volume change produced by temperature fluctuations. A motorized valve and temperature sensor control the EGW at 30.0 º C. The valve located in the water return line of the heat exchanger modulates the flow in response to changes in the EGW discharge temperature (Figure 1). Reviewing the PLMC cycle (Figure 2) shows 8.2 gpm of R-134a sub-cooled fluid discharging from the pump at 30.0 ºC (86.0 ºF) and 112.3 psig. The coolant flows into the EDA assembly and is uniformly distributed between the manifolds. Approximately 1.0 gpm of coolant passes through each manifold, isothermally cooling 6.8 kW of EDA power. This design is based on an EDA discharge quality of 50%. The mixture enters the separator (tube) at 32.0 ºC, 103.4 psig, and 50 % quality. Here gravity causes the saturated liquid to collect at the tube bottom displacing the saturated vapor. The vapor is condensed to a sub-cooled liquid leaving the condenser at 28 ºC and 103.4 psig. Prior to the pump both liquids mix to form a sub-cooled liquid at 30.0 ºC and 103.4 psig. Filter and miscellaneous line losses account for the remaining 0.5 psig. As in Figure 1 the reservoir compensates for volume changes due to fluctuation in temperature. In the unlikely event that the R-134a charge is compromised a sensor located at the top of the bleed line signals a controller to power down the system. A passive, low cost OEM flow control valve, regulated by pressure, maintains the R- 134a saturation pressure at 103.4 psig or 30 ºC. Enclosure 3 is a chart showing the system flow summary for R-134a. Included in the chart are the pump curve, the EDA baseline curve, and EDA design curve. Reviewing the results shows a system design point (DP) of 9.4 psid at 8.2 gpm (Enclosure1). To achieve the 9.4 psid an additional 6.3 psid of resistance is added to the 3.1 psid baseline value. The 6.3 psid resistance is added in the form of manifold metering orifices that augment the flow distribution. Enclosure 4 details the flow resistance data that characterize the PLMC system design. At the design flow of 8.2 gpm, Chart 1 shows a corresponding system resistance of 9.4 psid. This value consists of adding the 6.3 psid metering orifice resistance to the 3.1 psid EDA baseline. Chart 2 shows both the EGW and R-134a baseline system resistance curves. The R-134a curve is developed from EGW design criteria of 105 psig at 50 gpm. Extrapolating the R-134a data from 50 gpm to 8.2 gpm results in a baseline resistance value of 3.1 psid. Enclosure 5 is a load sensitivity study. Noted in the summary is the design point of 54.4 kW load and 50 % quality. Typical quality limits for the preferred operating range are 25% and 75%. The corresponding load limits for this design at 30.0 ºC (86.0 ºF) are 109.6 kW and 37.3 kW, respectively. To supplement the SBIR effort, Raytheon requested that a series of cursory heat exchanger tests be added. Raytheon supplied two similar aluminum heat exchangers identified by model numbers C-002 and C-007. Both heat exchangers were designed with off-set aluminum strip fins. Model C-002 contains 10 fins /inch (fpi) and model C-007, 24 fpi. Enclosure 10 shows the test data and results used to generate the charts of Enclosures 7 and 8. Enclosure 6 shows the R-134a test set-up and instrumentation. Inlet and outlet temperatures were measured at T 8 and T 9 , respectively. Pressure and pressures drop values were measured at P 2 and ΔP 1 , respectively. Flow rate values were taken from FM4. Two test series designed to determine the thermal performance of the heat exchangers operating as evaporators and 3
  • 4. condensers were performed. Enclosure 7 is a sketch of the heat exchanger test configuration. It shows a distribution manifold and off-set strip fin sandwiched between the top and bottom frames. Also shown on the frame top are the R-134a inlet and exit and the location of the thermocouple holes. Directly above the top and centered over the fins is a film heater (heat load). Covering the heater is a pad of thermal insulation used to limit heat losses. Section A-A details the cross section and shows the thermocouple holes and fin cavities. Enclosures 8 and 9 summarize the test results for the evaporators and condensers, respectively. The enclosures combine the thermal and flow resistance results into two charts for the 10 fpi and 24 fpi heat exchangers. A cursory examination of the thermal resistances show the 24 fpi heat exchanger values are lower than those of 10 fpi. Also, noted is the negligible difference in flow resistance values between the two exchangers. Enclosure 8, Chart 3 and Enclosure 9 Chart 5 summarize the thermal resistant results for the exchangers tested as evaporators and condensers, respectively. Test results show that Model C-007, 24fpi consistently has lower thermal resistance than Model C-002 10 fpi design. A comparison of the evaporator data at an exit quality of 30% shows the 10 fpi value of 0.011 deg C/W or 43% greater than the 0.006 deg C/W for the 24 fpi. Similarly, for the condenser at 30% inlet quality, the 10 fpi heat exchanger resistance is 0.011 deg C/W or 50 % greater than the 0.005 deg C/W for the 24 fpi heat exchanger. Enclosure 8, Chart 4 and Enclosure 9, Chart 6 compare the flow resistance of each exchanger tested as evaporators and condensers, respectively. Reviewing the charts shows little difference between both heat exchangers. Maximum resistance value for the evaporator is 0.52 psid and occurs at an exit quality of 18%. Correspondingly, the maximum condenser resistance is 1.4 psid at an inlet quality of 20 %. Enclosure 10 tabulates the heat exchanges test data and results used in Enclosures 8 and 9. Ten thermocouples located on the heat exchanges surface between the heater and the fins (Enclosure 7) provide temperatures data. These values are averaged and subtracted from the R-134a sink value (R-134a saturated discharge temperature). Note this value is T 9 for the evaporator and T 8 for the condenser. Correspondingly, the vapor quality is determined from the heat load, mass flow rate, and the vapor enthalpy. For example, Case no. 100 has an average surface temperature of 30.4 ºC (Tave) and a saturation temperature of 27.9 ºC (Tsat) or a 2.9 deg C difference. The corresponding load is 203.7 W, thus, the thermal resistance for this case is 0.0123 deg C/W. Determining the vapor quality requires converting 203.7 w to 695.2 Btuh, changing the 5.0 gal/hr to an equivalent mass flow rate of 9.9 lb/hr (pph), and obtaining the vapor enthalpy at 27.9 ºC. Enthalpy data taken from reference d shows a value of 75.9 Btuh/lb. The vapor quality determined from these values is 0.183 or 18.3 % Discussion of Results: The PLMC technology is based on pumping 2 deg C sub-cooled R-134a refrigerant through a heat exchanger (manifolds) where heat is transferred to the R-134a. The heat added to the R- 134a converts the sub-cooled liquid to a 32 ºC (90 ºF) isothermal mixture of saturated liquid and vapor, typically known as a quality mixture. More specifically, quality is the weight ratio of the vapor to the total weight of the mixture. As the mixture exits the heat exchanger it passes into a long vertical tube called a separator. Here gravity causes the 32.0 ºC saturated liquid to collect at the tube bottom displacing the vapor. The saturated liquid passes from the separator to a mixing port upstream of the pump. The displaced vapor (32.0 ºC) passes through the condenser and exits as a sub-cooled liquid at 28.0 ºC (4.0 deg C of sub-cooling). Combining the fluids at the mixing port forms a 30.0 ºC sub-cooled liquid. Figure 2 of Enclosure 2 shows the 50% quality mixture splitting into 41.1 lb/min (ppm) of saturated liquid collecting at the bottom of the 4
  • 5. separator and 41.1 ppm of vapor flowing to the condenser. To prevent condensate from collecting on the external surfaces of the hardware, the R-134a (coolant) is maintained above the local dew point temperature. A 30.0 ºC (86.0 ºF) value is specified in the design criteria. A passive low cost OEM control required for maintaining the coolant temperature also makes it possible to simply change the R-134a operating temperature. Enclosure 5 addresses the sensitivity of the system to changes in cooling load. The PLMC operating envelope for a design flow of 8.2 gpm and 30.0 ºC ranges from 109.6 kW to 37.3 kW. However, the quality changes correspondingly from 25% to 75%. Potential changes to the pump speed due to line voltage fluctuation or other minor aberrations have no effect on the cooling performance of the system. However, any changes made in the heat load need to be followed by changes in the condenser performance. A specific request to measure the flow resistance of the fins only was made. Initial measurements were inconclusive. Further investigation concluded that the measured values were outside the resolution of the available test equipment. A default test that included the manifold was adopted. Enclosure 8, Chart 4 and Enclosure 9, Chart 6 summarize the flow resistance results for the heat exchangers. Both charts show that the 10 and 24 fpi flow resistance values coincide. An explanation of this is found in the heat exchanger distribution manifold design (Enclosure 7). The manifold governs the heat exchange flow resistance and is designed with several times the resistance of the fins, thus, making the fin resistance values insignificant. The PLMC design results show that a R-134a EDA cooling system is a viable alternative to the EGW platform. In summary, for the same design constraints as the EGW platform, the PLMC delivers the same cooling performance at a lower coolant flow rate and subsequently lower pressure drops. The package envelope and weight are considerably less. Parasitic power requirement and hardware costs are lower. Critical to the product development cycle is validating the design by building and testing a proof- of-concept model. Therefore, it is recommended that a phase 2 SBIR proposal effort be immediately addressed. Conclusions: The PLMC cooling technology provides a new and effective alternative to today’s conventional design strategies. Visions of the PLMC technology beyond this study are major and complement the technical challenges of the United States and the world. Adapting the PLMC cooling technology into future U.S. defense projects will lower parasitic power demands, reduce package envelope and weight, lower hardware costs, provide isothermal cooling, and widen operating envelopes. These attributes support the philosophy of a lighter, faster, more effective military at lower costs. One major commercial contribution of the PLMC technology is in reducing the amount of waste energy consumed by the world computer service industries. It is estimated that 40% of the energy budgeted for cooling computers is used to maintain the computer room environments. Most of this energy is used to power computer room fans and blowers to augment the cooling process. By replacing the fans and blowers with the PLMC technology significantly reduce the 40% waste heat. TFF’s current model mounts cold plates to temperature sensitive components. Manifolds within the cabinet distribute and collect the R-134a coolant. Heat generated by the component isothermally changes the R-134a from a liquid to a vapor. Conversely, as the vapor flows through the condenser, heat is transferred to the cooling media (water or air) converting the vapor back to a liquid. By placing the condenser external to the building, the heat is 5
  • 6. transferred outside, thus, eliminating a significant amount of the fan and blower power requirements. Other commercialized avenues targeted for PLMC technology include laser technology, power and power supplies, astronomy, medicine, and transportation. 6
  • 7. Enclosure 1 SUMMARY OF RESULTS Reference Items Design Constraints System Design % Change (Raytheon) (TFF) System Performance Cooling Media Single Phase EGW 2 Two Phase R-134a Quality (%) NA 50 NA Heat Load (kw) 54.4 54.4 NA Flow Rate (gpm) 50.0 8.2 -84 Coolant Temperature ( C ) 30.0 30.0 0 Max. Pressure (psig) 125.0 112.3 -10 Pressure Drops (psid) 105.0 9.4 -91 EDA Manifold Load (kw) 6.8 6.8 NA Coolant Temp ( C ) 30 in / 35 out 32 in / 32 out NA Flow Rate (gpm) 6.3 1.0 -84 Critical Temperatures ( C ) 38.0 34.0 NA Pressure Drops (psid) 100.0 8.9 -91 Heat Exchanger3 Type EGW Vapor NA Size (Tons) 15.5 15.5 NA Flow Rate (gpm) 50.0 50.0 NA Supply Pressure (psig) 20.0 20.0 NA Supply Temperature ( C ) 15.0 15.0 NA Pump (centrifugal) HP 10.0 0.2 -98 Wt (Lb) 300.0 25.0 -92 Envelope (in) TBD 26quot; x 16quot; x 10quot; TBD System Impact Leakage1 Contamination Potenial None NA Hardware Reliability (khrs) No Data 50 TBD Size 60quot;L x 30quot;W x 60quot;H 25quot;L x 15quot;W x 45quot;H -84 Weight (Lb) 874.0 150.0 -83 Power (kw) 7.5 0.1 -98 Hardware $11,340.00 ~ $6500.00 -43 1. Impact on leakage on electrical circuits 2. Single Phase EGW (55/45 by Vol) 3. Water Cooled Heat Exchanger 7
  • 8. Enclosure 2 COOLING CYCLE FLOW DIAGRAMS 8
  • 9. Enclosure 3 SYSTEM FLOW SUMMARY 20.0 Notes: 1. Manufacturer….DTE Energy Technologies PREFERRED OPERATING RANGE 2. Model ………..…HY-SAVE Model # 820 HYS 3. Part Number…...820-00-HYS 4. RPM…………….3550 16.0 5. Fluid…………….R-134a 5. Tsat………….… 30 C (86 F) Pump 6. Quality ………… 50% Pressure Drop (dP) / psid Performance EDA Design (R-134a) 12.0 9.4 DP 8.0 Metering Orifice (6.4 psid) EDA Baseline ( R-134a) 4.0 3.1 8.2 0.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.0 Volumetric Flow rate (V) /gpm 9
  • 10. Enclosure 4 FLOW RESISTANCE Chart1: System Flow Resistance 100.0 Notes: 1. Coolant…………………..R -134a 2. Coolant Tem ( C )…………..30 p E Design DA Metering Orifices Pressure Loss (dP) / pisd 10.0 9.4 E Baseline DA 6.3 3.1 1.0 8.2 0.1 1 10 100 Flow Rate (V) / gpm Chart 2: EDA Baseline Flow Resistance 1000.0 Notes: 1. Coolant Temp ( C )………..30 Pressure Loss (dP) / pisd 100.0 105 EGW Baseline 10.0 R-134a Baseline 3.1 50 8.2 1.0 1 10 100 Flow Rate (V) / gpm 10
  • 11. Enclosure 5 LOAD SENSITIVITY 160 Notes: Coolant…………..R-134a 140 Tsat ……………...30 C (86 F) Flow ……………..8.2 gal/min 120 PREFERRED OPERATING RANGE 109.6 Load (P) / kw 100 80 60 54.4 Design Goal 40 37.3 20 0 0 10 20 30 40 50 60 70 80 90 Design Quality (X) / % 11
  • 12. Enclosure 6 TEST FIXTURE AND INSTRUMENTATION 12
  • 13. Enclosure 7 HEAT EXCHANGER A 0.38”T x 2“W x 4”L Thermal Insulation 2”x4” Film Heater (Load) Inlet Thermocouple Locations 10 plc’s) Exit Distribution 0.10”Tx2.0” W x4.0” L Manifold Off-Set Strip Fine A 0.84”Tx 4.0”W x11.75” L Aluminum Heat Exchanger Frame (Bottom) 0.84”Tx 4.0”W x11.75” L Aluminum Heat Exchanger Frame (Top) Thermocouple Holes Locations (10) 0.05”Tx2” W x11.0”L Off-Set Fin Cavity (Top) 0.10”Tx2.0” W x4.0” L Off-Set Strip Fine 0.05”Tx2” W x11.0” L Off-Set Fin Cavity (Bottom) Section A-A 13
  • 14. Enclosure 8 EVAPORATOR TEST RESULTS Chart 3: Thermal Resistance 0.014 0.013 Thermal Resistance / deg C-wt -1 0.012 0.011 10 fins/inch (C-002) 0.010 0.009 0.008 24 fins/inch (C-007) 0.007 0.006 0.005 0.004 0 10 20 30 40 50 60 70 80 90 100 Exit Quality (%) Chart 4: Flow Restance 1.00 Pressure Loss / psid 24 fin/inch 10 fins/inch 10 fins / inch 24 fins/inch 0.10 - 0.01 - 10 100 Exit Quality (X) / % 14
  • 15. Enclosure 9 CONDENSER TEST RESULTS Chart 5: Thermal Resistance 0.014 0.013 Thermal Resistance / deg C-W -1 0.012 10 fins/inch (C-002) 0.011 0.01 0.009 0.008 0.007 0.006 24 fins/inch (C-007) 0.005 0.004 0 20 40 60 80 100 120 Inlet Quality (%) Chart 6: Flow Resistance 10.0 Pressure Drop / psid 24 fins/inch 1.0 10 fins/inch 0.1 10 Inlet Quality (%) 100 15
  • 16. Enclosure 10 HEAT EXCHANGER TEST DATA AND RESULTS Heat Exchanger ID Fins/Inch 10 24 PN 49956-H335240-1 49956-H335240-1 MFG 1TL57 1TL57 SERNO C-002 C-007 Evaporator Case No 100 101 102 103 104 105 112 113 114 115 116 117 FINS/INCH 10 24 Temperatures CldPlt 1 (C) 28.7 28.6 28.9 29.2 29.1 29.8 28.6 28.6 28.7 28.9 29.3 30.1 CldPlt 2 (C) 30.7 30.4 30.7 31.1 31.1 31.9 29.8 29.5 29.6 30.0 30.7 31.8 CldPlt 3 (C) 31.3 31.1 31.3 32.3 32.5 33.3 31.1 30.9 31.1 31.9 32.9 34.0 CldPlt 4 (C) 31.2 30.9 31.3 32.5 32.9 33.6 30.2 29.9 30.0 30.7 31.9 33.1 CldPlt 5 (C) 29.6 29.4 29.6 30.7 31.0 31.7 28.9 28.6 28.6 29.0 29.7 30.7 CldPlt 6 (C) 29.1 28.9 29.2 29.5 29.3 29.8 28.3 28.2 28.2 28.4 28.6 29.4 CldPlt 7 (C) 30.9 30.5 30.7 31.2 31.0 31.6 30.2 29.8 29.7 30.0 30.4 31.3 CldPlt 8 (C) 32.7 32.4 32.7 33.7 33.8 34.4 30.6 30.2 30.2 30.7 31.4 32.5 CldPlt 9 (C) 30.7 30.4 30.5 31.6 31.9 32.7 29.6 29.3 29.2 29.5 30.3 31.6 CldPlt 10 (C) 29.3 29.0 29.2 30.0 30.3 31.0 28.7 28.3 28.3 28.4 28.8 29.7 T8 (C) 27.2 27.4 27.7 28.1 27.9 28.4 27.0 27.5 27.6 28.0 28.1 29.0 T9 (C) 27.9 27.9 28.2 29.1 29.2 29.7 28.1 27.9 28.1 28.2 28.6 29.4 Sensors V1 (gph) 5.0 4.0 3.0 2.0 1.5 1.0 5.0 4.0 3.0 2.0 1.5 1.0 P2 (psia) 103.7 103.1 104.1 104.4 103.0 103.4 103.9 103.4 103.4 103.6 103.3 102.9 dP1 (psid) 0.497 0.356 0.222 0.098 0.048 0.011 0.519 0.361 0.223 0.104 0.043 0.010 Results Tave (C) 30.4 30.2 30.4 31.2 31.3 32.0 29.6 29.3 29.4 29.8 30.4 31.4 Tsat (C) 27.9 27.9 28.2 29.1 29.2 29.7 28.1 27.9 28.1 28.2 28.6 29.4 Load (w) 203.7 203.7 203.7 203.7 203.7 203.7 204.6 204.6 204.6 204.6 204.6 204.6 R (deg C/w) 0.0123 0.0112 0.0106 0.0102 0.0104 0.0110 0.0075 0.0072 0.0063 0.0076 0.0089 0.0102 Exit Quality (%) 18.3 22.9 30.5 45.8 60.8 91.4 18.4 22.9 30.6 45.9 61.2 91.7 Condenser Case No. 118 119 120 121 122 123 130 131 132 133 134 135 FINS/INCH 24 Temperatures CldPlt 1 (C) 26.9 26.7 26.8 26.8 26.8 26.9 26.0 25.8 25.8 25.8 25.7 25.8 CldPlt 2 (C) 26.9 26.8 26.9 26.8 26.7 26.8 25.4 25.3 25.5 25.5 25.3 25.4 CldPlt 3 (C) 27.2 27.1 27.1 27.0 27.0 27.0 26.1 26.0 26.2 26.2 26.1 26.2 CldPlt 4 (C) 27.3 27.2 27.2 27.1 27.1 27.1 27.3 27.2 27.4 27.4 27.3 27.3 CldPlt 5 (C) 27.4 27.2 27.2 27.1 27.1 27.1 26.8 26.7 26.9 26.8 26.6 26.7 CldPlt 6 (C) 25.9 25.7 25.8 25.8 25.8 25.9 24.7 24.5 24.7 24.8 24.7 24.8 CldPlt 7 (C) 25.8 25.6 25.8 25.8 25.8 25.8 23.8 23.8 23.9 24.0 23.8 23.9 CldPlt 8 (C) 26.8 26.7 26.7 26.7 26.6 26.7 24.8 24.8 24.9 25.0 24.9 24.9 CldPlt 9 (C) 27.1 26.9 27.0 26.9 26.8 26.9 25.9 25.8 26.0 26.0 25.9 26.0 CldPlt 10 (C) 27.3 27.2 27.2 27.1 27.0 27.1 26.6 26.5 26.6 26.6 26.4 26.5 T8 (C) 28.0 27.8 27.9 27.7 27.7 27.7 28.2 28.0 28.1 28.0 27.9 27.9 T9 (C) 27.9 27.7 27.8 27.6 27.6 27.6 28.1 27.9 28.0 27.9 27.8 27.9 Sensors V1 (gph) 5.0 4.0 3.0 2.0 1.5 1.0 5.0 4.0 3.0 2.0 1.5 1.0 P1 (psia) 104.1 103.6 103.6 103.3 103.2 103.3 104.1 103.7 103.3 103.1 102.8 103.3 dP1 (psid) 1.38 1.17 0.98 0.77 0.69 0.61 1.33 1.16 0.97 0.76 0.70 0.63 Results Tave ( C) 26.8 26.7 26.8 26.7 26.7 26.7 25.7 25.6 25.8 25.8 25.7 25.8 Tsat ( C) 28.0 27.8 27.9 27.7 27.7 27.7 28.1 28.0 28.1 28.0 27.9 27.9 Load (wt) 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 207.1 R (deg C/wt) 0.0058 0.0054 0.0053 0.0050 0.0050 0.0050 0.0115 0.0115 0.0114 0.0106 0.0106 0.0105 Inlet Quality (%) 20.4 25.5 33.9 50.9 67.8 101.7 20.4 25.5 33.9 50.8 67.7 101.7 16
  • 17. Enclosure 11 PUMP RELIABILITY Hy-Save Energy Conservation Technologies PO Box 631 4701 Ridge Road Cazenovia NY 13035 Phone 315 655 3322 Fax 315 655 4539 E-mail hysaveect@aol.com August 23, 2001 To: Joe Marsala From: Walter Joncas Subject: Refrigerant pump reliability I will attempt to keep this short and to the point. After Studies conducted by the National Institute of Standards and Technology (NIST) were completed and a public report filed The Federal Energy Management Program (FEMP) published its report in 1995 on the Hy-Save Pump. On the first page of the FEMP report it states that the Hy-Save Pump was “ultra reliable”. That finding is a result of The US Governments, Pacific Northwest Laboratory, Richland Washington study of the Hy-Save Pump over a two-year period. In support of that study an audit of all repair parts sold by Hy-Save for any reason was conducted. At that point in time 12,500 refrigerant pumps had been installed primarily in refrigeration systems. Sixty million operating hours is estimated based on 10,000 of the pumps operating at least 6000 hours per year in a full time refrigeration environment. A total of 124 impeller / shaft replacements were made during this same time period. Of the 124 impeller / shaft sets replaced, 60 were replaced as a result R&D testing of materials. Forty three of the Impeller / shaft assemblies were damaged by running dry due to improper piping practice and or loss of refrigerant through a leak elsewhere in the host system. This caused the bearings to overheat thus causing failure. The remaining 21 sets showed signs of bearing material breakdown. At least 10 of those were due to contamination within the system. There were 11 failures of unknown origin. No (of what could be considered normal), worn out impeller bearings or shafts causing failure were observed. On a more localized basis, and specific to the pump you are using, the east coast suppliers (Cazenovia, New York, Gainesville, Florida) have not shipped any replacement parts for the model 809IND for any reason to any point east of the Mississippi in the past four years with one exception. The exception is Thermal Form and Function, Manchester MA. Spare parts have been shipped and inventoried at their location but those parts have not been used. I could not confirm what was shipped west of the Mississippi in exact terms during this same time period. However I have strong reason to believe the number was less than three. 17