SlideShare une entreprise Scribd logo
1  sur  70
Boiler System
Date: 06/06/2017
By Wasiullah
BOILER:
A boiler is defined as "a closed vessel in which water or other
liquid is heated, steam or vapor is generated, steam is
superheated, or any combination , under pressure or vacuum,
for use external to itself, by the direct application of energy
from the combustion of fuels, from electricity or nuclear
energy."
Types of Boiler:
1) Fire Tube Boiler
2) Water Boiler
Fire Tube Boiler:
The fire tube boiler design uses tubes to direct the hot gases
from the combustion process through the boiler to a safe point of
discharge. The tubes are submerged in the boiler water and
transfer the heat from the hot gases into the water.
Types of fire-tube boiler
• Cornish boiler.
• Lancashire boiler.
• Scotch marine boiler.
• Locomotive boiler.
• Vertical fire-tube boiler.
• Horizontal return tubular
boiler.
• Immersion fired boiler.
• Cornish boiler :
Cornish boiler is a simple horizontal
boiler which belong to the shell and tube
class of boilers. Cornish boiler is much like
the Lancashire boiler. Cornish boiler has the
ability to produce steam at the rate of 1350
kg/hr and can take the maximum pressure of
about 12 bar. Dimensions of the Cornish
boiler shell is 4 m to 7 m in length and 1.2 m
to 1.8 m in diameter.
• Lancashire boiler:
The Lancashire boiler is similar to the
Cornish, but has two large flues containing
the fires instead of one. It is generally
considered to be the invention of William
Fairbairn in 1844, although his patent was
for the method of firing the furnaces
alternately, so as to reduce smoke, rather
than the boiler itself.
• Scotch Marine Boiler:
The Scotch Marine Boiler is a
fire-tube boiler, in that hot flue gases
pass through tubes set within a tank
of water. The general layout is that of
a squat horizontal cylinder. One or
more large cylindrical furnaces are in
the lower part of the boiler shell.
Above this is a large number of
small-diameter fire-tubes.
• Locomotive boiler:
Locomotive boiler is the horizontal
fire tube boiler in which hot gases pass
through the tubes and water surrounds
them. Transferred heat from the gases
to water and then converted into
steam. It may also be used as a
stationary boiler.
• Vertical fire-tube boiler :
A vertical fire-tube boiler or vertical
multitubular boiler is a vertical boiler where
the heating surface is composed of multiple
small fire-tubes, arranged vertically. These
boilers were not common, owing to
drawbacks with excessive wear in service.
The more common form of vertical boiler,
which was very similar in external
appearance, instead used a single flue and
water-filled cross-tubes.
• Horizontal return tubular boiler:
A fire-tube boiler is a type of boiler in
which hot gases from a fire pass through
one or (many) more tubes running through a
sealed container of water. The heat of the
gases is transferred through the walls of the
tubes by thermal conduction, heating the
water and ultimately creating steam.
• The immersion fired boiler:
The immersion fired boiler is
a single-pass fire-tube boiler that
was developed by Sellers
Engineering in the 1940s. It has
only firetubes, functioning as a
furnace and combustion chamber
also, with multiple burner nozzles
injecting premixed air and natural
gas under pressure. It claims
reduced thermal stresses, and
lacks refractory brickwork
completely due to its construction
Water Tube Boiler:
The water tube boiler design uses tubes to direct the
boiler water through the hot gases from the combustion
process, allowing the hot gases to transfer its heat through the
tube wall into the water. The boiler water flows by convection
from the lower drum to the upper drum.
Types of Water Tube Boiler:
• Horizontal Straight Tube Boiler.
• Bent Tube Boiler.
• Cyclone Fired Boiler
Burner is a mechanical device that burns a gas or liquid fuel
into a flame in a controlled manner.
Energy Efficient Burner:
An efficient burner provides the
proper air-to-fuel mixture
throughout the full range of firing
rates, without constant adjustment.
Many burners with complex linkage
designs do not hold their air-to-fuel
settings over time. Often, they are
adjusted to provide high excess air
levels to compensate for
inconsistencies in the burner
performance.
BURNER
Energy Saving Due to Installation of an Energy Efficient Burner
Burner Combustion
Efficiency Improvement %
Annual Energy Savings
(MMBtu/year)
Annual Savings ($)
1 6,250 28,125
2 12,345 55,550
3 18,290 82,305
Cost Savings = Fuel Consumption * Fuel Price * (1-E1/E2)
If the installed cost is $50,000 for a new burner that provides an
efficiency improvement of 2%, the simple payback on Investment is:
Simple Payback = $50,000 ÷ $55,550/ year = 0.9 Years
Example;
Even a small Improvement in burner efficiency can provide significant
savings. Consider a 50,000 pound per hour process boiler with a combustion
efficiency of 79% (E1). The Boiler annually consumes 500,000 million British
thermal units(MMBtu) of natural gas. At a price of $4.50/MMBtu, the annual
fuel cost is $2.25million. What are the saving from installing an energy
efficient burner that improves combustion efficiency by 1%, 2%, or 3 %.
• Perform burner maintenance and tune your boiler.
• Conduct combustion-efficiency tests at full- and part-load
conditions.
• If the excess O2 exceeds 3%, or combustion efficiency values are
low, consider modernizing the fuel/air control system to include
solid-state sensors and controls without linkage. Also consider
installing improved process controls, an oxygen trim system, or a
new energy-efficient burner.
• A new energy-efficient burner should also be considered if repair
costs become excessive, reliability becomes an issue, energy
savings are guaranteed, and/or utility energy-conservation rebates
are available.
• Install a smaller burner on a boiler that is oversized relative to its
steam load.
SUGGESTED ACTIONS
• Air Properties:
For a burner originally adjusted to 15 % air, changes in
combustion air temperature and barometric pressure cause the
following in excess air:
Expressed as a percent of the stoichiometric
air required.
PASSES OF BOILERS
Three-pass firetube boiler:
A 3-pass firetube boiler design
consists of three sets of horizontal
tubes, with the stack outlet
located on the rear of the boiler. A
downdraft design keeps the cooler
water from having an effect on
the hot surfaces within the boiler.
3 pass firetube boilers offer:
• maximized heat transfer
• minimal refractory
• high steam/water storage
• effective handling of wide
load demands
Four-pass boiler:
A four-pass boiler design consists
of four sets of horizontal tubes, with
the stack outlet at the front of the
vessel. A downdraft design keeps the
cooler water from having an effect
on the hot surfaces within the boiler.
4-pass boilers leverage natural draft
operation which allows cool water to
contact the hottest part of the boiler.
4 pass firetube boilers offer:
• maximized heat transfer
• minimal refractory
• high steam/water storage
• effective handling of wide
load demands
BOILER PERFORMANCE TEST
Performance of the boiler, like efficiency and evaporation ratio
reduces with time, due to poor combustion, heat transfer fouling and
poor operation and maintenance. Deterioration of fuel quality and
water quality also leads to poor performance of boiler. Efficiency
testing helps us to find out how far the boiler efficiency drifts away
from the best efficiency.
• To find out the efficiency of the boiler
• To find out the Evaporation ratio
The purpose of the performance test is to determine actual
performance and efficiency of the boiler and compare it with design
values or norms. It is an indicator for tracking day-to-day and season-
to-season variations in boiler efficiency and energy efficiency
improvements
1. Boiler Efficiency = Heat Output/Heat Input*100
= Heat In Steam Output(kCals)/Heat in fuel Input(kCals)*100
2. Evaporation Ratio = Quantity of Steam Generation/Quantity of Fuel Consumption
Heat recovery equipment is available to preheat feed water
entering the boiler (economizer) and to capture Btu’s lost
through boiler blowdown (blowdown heat recovery or flash
tank heat exchangers). Such equipment is normally used on
installations where boiler size, operating pressures or the
amount of water make-up justify the economics for the
purchase and installation costs (normally units exceeding
100 hp and operating at 100 psi or more). Maintenance
costs also must be considered before a decision is made for
their installation.
HEAT RECOVERY EQUIPMENT
Economizers are bent, finned-tube heat
exchangers. They are available in
rectangular or cylindrical styles. The
type of boiler and the overall boiler
room layout may dictate which style is
utilized.
The products of combustion leaving the
boiler flow through the economizer,
over the finned tubes, transferring its
heat or Btu’s to the boiler feed water.
The efficiency of the overall system can
be increased By 2% to 4%, depending
on fuel being burned, boiler size, and
operating conditions.
ECONOMIZERS
There are several methods and
equipment used in blowdown heat
recovery.
In most cases, the systems are used on
continuous or surface blowdown to
control the Total Dissolved Solids
(TDS) in the boiler water.
Blowdown heat recovery equipment
is used for automatic control of the
continuous blowdown, based on
water make-up and cools the
continuous blowdown to a point
where it can be safely dumped to the
sewer system. It transfers heat or
Btu’s to the make-up water, thus
raising the temperature of the make-
up water before it enters the deaerator
or boiler feed system.
BLOWDOWN EQUIPMENT
An additional piece of equipment, the
blowdown separator , can be installed for
bottom blowdown. The blowdown
separator reduces the temperature of the
bottom blowdown water to a temperature
that would be safe for the sewer system.
However, because of the erratic flow of
bottom blowdown, there is little benefit to
use a blowdown separator as a means to
raise the temperature of make-up water
prior to entering the deaerator or boiler
feed system.
BLOWDOWN SEPARATOR
Another system uses the
addition of a flash tank heat
exchanger. This system works
on the same principle as the
blowdown heat recovery
system, however, it also
provides the benefit of flash
steam. This flash steam can be
reused in the plant, such as
being piped to a deaerator and
mixed with the incoming steam
in the deaerator.
FLASH TANK HEAT EXCHANGER:
During daily operation of a plant, a
sample cooler is normally required to
draw samples of boiler water, so
chemical tests can be performed. The
boiler water, however, is above the
temperature that test equipment can
handle. In most cases, the situation is
resolved with the installation of a
sample cooler.
SAMPLE COOLER
Boiler feed water usually contains two
harmful dissolved gases: Oxygen and
Carbon Dioxide. If the dissolved gases are
not removed before entering the boiler, they
will be liberated by heat and may cause
severe corrosion in the boiler, steam lines,
condensate lines, and heat transfer
equipment, which can prove to be very
costly. The dissolved oxygen and carbon
dioxide can be removed with chemicals.
Depending on the overall system, it may not
be practical to chemically remove the
dissolved oxygen and carbon dioxide from
the feed water. In these cases, a deaerator
should be installed. Because the deaerator
mechanically removes dissolved oxygen
and carbon dioxide, the amount of
chemicals required could be reduced.
BOILER FEEDWATER EQUIPMENT
The deaerator is a pressurized
American Society of Mechanical
Engineers (ASME) tank and may be
the largest piece of auxiliary
equipment in the boiler room. A
deaerator is designed to heat water to
the temperature of saturated steam at
the pressure within the deaerator.
A deaerator provides an effective
means for recovery of heat from
exhaust or flash steam, provides a
location for returning condensate and
accepts condensate first to reduce
excessive make-up water. There are
three types of deaerators available.
The tray type is normally used in
large utility plants.
DEAERATORS
If plant conditions do not warrant the use of a deaerator, in most cases, a
Packaged Feed System is used. The packaged feed system is an atmospheric
tank that can heat feed water to a maximum of 210°F.
Because they are atmospheric tanks, they are equipped with an epoxy lining
or made from galvanized steel. The packaged feed system heats the feed
water and reduces the amount of dissolved oxygen and carbon dioxide in the
feed water.
There are many additional pieces of
equipment available to remove
impurities in the make-up water before it
enters the boiler and system. The type of
equipment required is determined by a
water analysis. This equipment can be
classified as pre-treatment equipment.
FEED SYSTEMS
Filters are available to remove
free chlorine, some dissolved
organics and sediment. They can
also remove suspended solids,
colloidal matter, sand and iron.
There are carbon filters,
multilayered filters, sand or iron
filters. There can be lined tanks,
American Society of Mechanical
Engineers (ASME) code tanks
and automatic operation based on
a time clock, pressure differential
switch or water meter. They can
protect such items as water
softeners, dealkalizers, and
reverse osmosis equipment, etc.
PRE-TREATMENT EQUIPMENT:
A surge tank could be used under the
following conditions: If there are
intermittent peak loads of condensate
that can exceed the surge capacity of
the deaerator - varying pressures or
temperatures in condensate – gravity
or pumped condensate that have
insufficient pressure to enter the
deaerator on their own. Surge tanks
are atmospheric and accept condensate
and make-up water before it goes to
the deaerator. Surge tanks can be lined
with an epoxy coating to prevent
corrosion. The condensate and make-
up water mix into a blend temperature
as determined by the percentage of
each.
SURGE TANK
The Flame Safeguard or Programming
Control on boilers are designed to ensure that
the start-up of the burner follows a definite
timed sequence of operation. In addition to
the sequence of operation and after the flame
has been established, the Flame Safeguard
monitors the flame and sets the firing rate of
the burner, as determined by the boiler firing
rate controls.
They also monitor, through the boiler controls, items such as boiler pressure or
temperature, fuel pressure or temperature and they provide for normal shut down of
the burner if the load demand is satisfied, or shut down and alarm if there is a safety
shut down condition.
The Flame Safeguards or Programming Control installed on a boiler can be
classified into three categories:
o Electro Mechanical
o Solid State Electronic
o Micro Processor
FLAME SAFEGUARD EQUIPMENT
The electro mechanical controls have been used from around 1950 until
1984.
Solid state electronic controls were introduced in 1984. This type of control
provides for more alarm or monitoring functions than the electro mechanical
controls. The micro processor controls introduced in 1989 not only provide
the functions as the other controls, but also have the ability to send
information to computers and work in conjunction with some energy
management systems. The micro processor type of controls are standardly
furnished on some of today’s modern boilers.
Solid state electronic controlsElectro mechanical controls
After the initial inspection is completed, the new boiler is ready for
startup. Startup can be the most critical period in the life of the
boiler.
1. Steam piping, blow off and blowdown lines, etc. must be
inspected and ready for operation. All piping must be inspected
for adequate support and expansion provisions.
2. All fuel supply lines must be checked for tightness and leaks.
Strainers are most important to the safe operation of gas and/or
oil fired units.
3. Electrical power lines to the boiler/burner unit are connected
and the voltage required is verified.
4. Hydrostatic test has been completed.
5. Any walkways, platforms, stairs, and/or ladders, etc., that are
needed to permit proper access to the boiler/burner, are installed
and ready for use.
BOILER STARTUP
Before the boiler is permitted to go on the line, all of the safety controls
should be checked to make sure they are all operating properly.
Flame Safeguard:
The purpose of the flame safeguard control is to monitor the burner start
up sequence, the main flame and control the firing rate during normal
operation.
Following is a brief step-by-step:
1. The burner switch is turned on or the operating limit pressure (or
temperature) control closes. If all required limit controls are
satisfied, the blower motor starts and the automatic sequence
begins.
2. The programmer actuates the modulating motor and drives it to
high fire position and purges the boiler for a predetermined period
of time.
3. The programmer drives, modulating motor and burner linkage back
to low fire position.
BOILER CONTROLS
4. The ignition transformer is energized and the pilot solenoid
valves are opened. The pilot must light.
5. Trial for ignition period.
6. If the pilot flame is proven, the programmer, after a timed
interval, energizes the main flame fuel valve(s) and trial for
main flame is started, at minimum fuel rate.
7. After a timed period, the main flame has to be established. If
this is completed, the programmer extinguishes the pilot and
then continues to monitor the main flame.
8. The programmer continues to monitor the main flame while the
burner continues to automatically modulate (if the burner is
capable of full modulation) on an increasing or decreasing
firing rate to satisfy the load demand.
9. The programmer cycles to off position and is now ready for
restart upon demand.
1. Know your equipment.
2. Maintain complete records.
3. Establish a regular boiler inspection schedule. The schedule
should include daily, weekly, monthly, semi-annual and annual
inspections or activities.
4. Establish and use boiler log sheets. Log sheets should be tailored
to your equipment.
5. Establish and keep written operating procedures updated.
6. Good housekeeping is a must.
7. Keep electrical equipment clean.
BOILER ROOM CARE
1. Check water level. Ensure there is water in the gauge glass every time
you enter the boiler room.
2. Blow down boiler. Blow down the boiler in accordance with the
recommendation of your feedwater consultant.
3. Blow down the water level controls to purge the float bowl of
possible sediment accumulation. Operating conditions will dictate
frequency of this check.
4. Check combustion visually. Look at the flame to see if something has
changed.
5. Treat water according to the established program. Add chemicals and
take tests as outlined by your chemical feedwater consultant.
6. Record boiler operating pressure or temperature.
7. Record feedwater pressure and temperature.
8. Record stack temperature. Changes in stack temperatures could
indicate the boiler is sooting, scaling or there is a problem with
baffles or refractory.
DAILY MAINTENANCE
9. Record oil pressure and temperature.
10. Record oil atomizing pressure. Changes in pressure could have
an effect on combustion in the boiler.
11. Record gas pressure. Changes in pressure could have an effect
on combustion in the boiler and indicate a problem in the gas
delivery system.
12. Check general boiler/burner operation. Maintaining top
efficiency is the simple and basic reason for having operating
personnel. Is anything different than it was the day before? If so,
why?
13. Record boiler water supply and return temperatures. On hot
water boilers, record these temperatures to assist in detecting
system changes.
14. Record makeup water usage. Excessive makeup water could be
an indication of system problems in both steam and hot water
systems.
15. Check auxiliary equipment.
1. Check for tight closing of fuel valves.
2. Check fuel and air linkages.
3. Check indicating lights and alarms.
4. Check operating and limit controls.
5. Check safety and interlock controls.
6. Check operation of water level controls.
7. Check for leaks, noise, vibration, unusual conditions, etc. Checking
for these items is a cost effective way to detect system operational
changes. Small problems can be corrected before they become
large problems.
8. Check operation of all motors.
9. Check lubricating levels.
10. Check the flame scanner assembly.
11. Check packing glands on all pumps and metering devices.
12. Check gauge glass. Ensure there are no cracks or etching in the
glass or leakage around the packing.
WEEKLY MAINTENANCE
1. Inspect burner operation.
2. Analyze combustion.
3. Check cams. Inspect the cam springs for scoring, tightness of set
screws, free movement, alignment of cam followers and other
related parts.
4. Check for flue gas leaks.
5. Inspect for hot spots. Inspect the boiler to ensure no hot spots are
developing on the outside of the boiler.
6. Review boiler blowdown to determine that a waste of treated water
is not occurring.
7. Check all combustion air supply inlets to the boiler room and burner
to ensure sufficient air is being supplied.
8. Check all filter elements. Clean or replace as needed
9. Check the fuel system to make certain that strainers, vacuum
gauges, pressure gauges and pumps are properly cared for.
10. Check all belt drives for possible failure.
MONTHLY MAINTENANCE
1. Clean low water cutoff . Remove the head assembly or probes and
inspect and clean out any sediment or contamination in the column
or piping.
2. Check oil preheaters by removing the heating element and inspect
for sludge or scale.
3. Repair refractory. Immediately upon opening the fireside areas, give
the refractories an inspection and start repairs as soon as possible.
4. Clean oil pump strainer and filter.
5. Check pump coupling alignment.
6. Reset Combustion. The entire combustion process should be
carefully checked, O2 readings taken and necessary burner
adjustments made.
7. Inspect mercury switches. Inspect mercury switches for
contamination, loss of mercury, and cracked or broken wires.
Replace if any of these conditions are found.
SEMI-ANNUAL MAINTENANCE
1. Clean fireside surfaces by brush or use a powerful vacuum cleaner to
remove soot.
2. Clean breeching. Inspect breeching and stack and remove any soot build
up.
3. Clean waterside surfaces. Remove all hand hole and manway plates,
inspection plugs from water column tees and crosses and float
assemblies from water columns.
4. Check fluid levels on all hydraulic valves. If any leakage is apparent,
take positive corrective action immediately.
5. Check gauge glass for possible replacement. If internal erosion at water
level is noted, replace with new glass and gaskets.
6. Remove and recondition safety valves. Have them reconditioned by an
authorized safety valve facility.
7. If oil fuels are used, check on the condition of the fuel pump. Fuel pumps
wear out and the annual inspection time is the opportune time to rebuild
or replace them.
ANNUAL MAINTENANCE
9. Boiler feed pumps. Strainers should be reconditioned.
10. Condensate receivers should be emptied and washed out. Make
an internal inspection, if possible.
11. Chemical feed systems should be completely emptied, flushed
and reconditioned. Metering valves or pumps should be
reconditioned at this time.
12. Tighten all electrical terminals. All terminals should be
checked for tightness, particularly on starters and movable
relays.
13. Check linkages. Check to ensure the linkage ball connectors
have not worn out. Worn connectors can cause inconstancy in
the linkage movement and result in unrepeatable excess air
levels in the combustion process.
1. The boiler room is for the boiler.
The boiler room should not be considered an all-purpose storage
area. The burner requires proper air circulation in order to prevent
incomplete fuel combustion and production of carbon monoxide.
Therefore, keep the boiler room clean and clear of all unnecessary
items.1.
2. Knowledge is powerful, as are boilers.
Ensure all personnel who operate or maintain the boiler room are
properly trained on all equipment, controls, safety devices, and
up-to-date operating procedures.1.
3. Look for potential problems.
Before startup, ensure the boiler room is free of all possibly
dangerous situations, such as flammable materials or mechanical
or physical damage to the boiler or related equipment. Clear
intakes and exhaust vents; check for deterioration and possible
leaks.
BOILER ROOM GUIDELINES
4. Observe new equipment.
Monitor all new equipment closely until safety and efficiency are
demonstrated.
4. Develop a maintenance schedule.
Use boiler operating log sheets, maintenance records, and
manufacturers’ recommendations to establish a preventive
maintenance schedule based on operating conditions, as well as on
past maintenance, repairs, and replacements performed on the
equipment.
6. Inspection matters.
Ensure a thorough inspection by a properly qualified inspector,
such as one who holds a National Board commission.
7. Reinspection matters, too.
After any extensive repair or new installation of equipment, make
sure a qualified boiler inspector reexamines the entire system.
8. Create thorough checklists.
Establish a checklist for proper startup and shutdown of
boilers and all related equipment according to manufacturers’
recommendations.
9. Don’t overlook automated systems.
Observe equipment extensively before allowing an automated
operation system to be used with minimal supervision.
10. Keep safety at the forefront.
Establish a periodic preventive maintenance and safety
testing program.
STEAM TRAPES
1.) Points about the steam trap
a. Mechanical steam trap
b. (On/Off Operation)
c. Test point – downstream of the discharge orifice
2.) Visual inspection
a. Steam trap should be level to the eye
b. Check flow arrow to insure steam trap is installed correctly
3.) Temperature measurement
a. Take temperatures before and after steam trap
b. Temperatures below 212°F or 100°C, steam trap is not in
operation
c. Take temperature at the process inlet. Temperatures at the process
inlet and the steam trap inlet will be relatively close.
4.) Off position during operation
a. Ultrasound level should be low
or zero on the ultrasound meter
b. Long off periods can cause
“loss of prime”
5.) Discharge Operation (discharging condensate)
a. When the inverted bucket drops due to the loss of buoyancy, this
will bring the valve away from the discharge orifice. This action
will allow the steam trap to discharge the condensate.
b. The ultrasound indicator will rise due to the increase in ultrasound
from the discharge cycle. The ultrasound will stay high or full scale
until condensate is discharged from the steam trap. The ultrasound
level (meter) should deflect more than 30% of scale.
c. When condensate is
completely discharged, the
inverted bucket will rise,
due to buoyancy, and bring
the valve in contact with the
discharge orifice .The steam
trap is now in the off
position. The ultrasound
level should be at zero or
minimum.
d. Ultrasound level should proceed to full or high ultrasound level
during the discharge cycle and return to minimum scale reading or
zero after the discharge is complete.
e. Condensate will crackle and steam will whistle during testing with
the ultrasound equipment, therefore during the cycling there will
be a crackling + whistling sound during the discharge cycle (steam
and condensate passing through the orifice of the steam trap).
f. The steam trap should stay in the off position for a least 15 seconds
before cycling (less than 15 seconds if the steam trap is
undersized)
g. Discharge – ultrasound meter should increase the ultrasound level.
h. The steam trap has a fast on/off operation.
6.) Light Condensate Load Operation
a. Ultrasound levels will cycle on and
off at low ultrasound levels. This is an
indication of low condensate flows.
7.) Failure Modes
a. Leaking steam
Steam trap valve wear or linkage will cause the steam trap to
leak steam. The following are indicators of leaking steam:
• Ultrasound meter does not return to zero or baseline
after condensate discharge cycle.
• Ultrasound levels are continuous off base line and there
is not distinct cycle/no cycle operation.
b. Blowing steam
Steam trap valve or linkage
failure or over sizing (loss of
prime) will cause the steam
trap to blow steam directly
through the steam trap.
The following are indicators
of leaking steam:
• Ultrasound meter is at
full scale.
• Hearing a dominant
whistling sound and no
crackling.
STEAM AND CONDENSATE
SYSTEMS
STEAM SYSTEMS IN INDUSTRY
AND OTHER SECTORS
• Steam can be used for heating, drying, moistening and
sterilization of products in industry and other fields
• Steam has advantages in effective heat transfer, indirect or
direct heating and hygienic.
• Special attention shall be given in productivity of steam
production (exhaust gas and blowout losses), distribution
networks and steam users.
• Water treatment and high maintenance needs may increase
operating costs.
STEAM PRODUCTION
• Steam can be produced by steam boilers and steam generators.
• Key factors in economic steam production
o boiler plant
o continuous consumption monitoring
o skilled personnel
• Considerations in boilers
o boiler capacity meets steam requirements
o meters are in good condition
o out-blow is not excessive
o economizer is in operation
o heat transfer surfaces are clean
o boiler has no air leakages
o boiler insulation is in good condition
STEAM NETWORKS
• Steam use can be either direct or
indirect, but the used energy
amount is the same, but heat
losses may differ.
• In direct use the valuable
condensing water return shall be
checked regularly
• Superheated steam has lower heat
transfer coefficient than saturated
steam
• Moist steam stress equipment
more than dry steam
• Air mixed in steam reduces the
heat transfer coefficient
LEAKAGES
• Leaks in steam systems
o waste continuously energy (24/7)
o reduce network pressure and energy
flow
o waste valuable condense water
(treated water)
o reduce work safety (blasts)
• To be checked visually or with ultrasonic
detector
o safety valves, steam traps, orifice
connectors, gate valves, unattended
pipe-tunnels
o leakage inspections shall be made at
least twice per year
PIPE AND EQUIPMENT INSULATION
• Pipes, flanges, equipment and
valves shall be insulated
because of heat losses and
working safety
• Condense pipes always
insulated, except condense
valves
• Wet insulation causes energy
waste and outside corrosion
• Un-insulated DN 200 valve
may have up to 200 C
temperature and 5 kW
continuous heat loss
CONDENSE RETURN
• Condense return is important in indirect steam use. Condense
traps are important.
• Precise condense return causes:
o good utilization of condense heat content
o reduction in make-up water needs
• Closure of open condense tank causes
o reduction in heat loss
o reduction in tank corrosion
• Condense tank should be blanketed from oxygen entry by steam
etc
FAILURES IN CONDENSE TRAPS
• Condense return rate shall be monitored and maximized
• Fault trap causes steam-condense mix in condense pipe
leading to increased temperate and backpressure, increased
steam consumption, higher condense and high feed water
pumping costs
• Faults in condense traps should be seek by listening (man /
machine) and by temperature metering (every 2 to 4
months)
UTILIZATION OF BLOWOUT STEAM
• Benefits of blowout
o Reduced steam
consumption
o Lost blowout steam
reduces
o Capacity of condensing
network increases
• Utilization of blowout steam
o Blowout steam usage in
low pressure systems
o Preheating of combustion
air, compressed air and
rooms
o Heating of sub-cooled
condense or preheating of
process-water in condense
tank
ECONOMICAL USE OF STEAM
• Steam pressure
o Is defined by required temperature /pressure level
o It is important that temperature/pressure meets the
user requirements
o It is important that pressure fluctuation is as small
as possible
o Steam networks can be divided by pressure
reduction valves to different pressure subnets
EQUIPMENT CONSIDERATIONS
• Very important that process automation works properly
• Steam network and equipment shall be started slowly
• Steam heated equipment shall have thermal insulation
• Open liquid surfaces shall be covered against evaporation
• Bypass valves shall be kept closed and watertight
• Minimization of steam pressure, finally replacing steam with
hot water
• Drying first by mechanical water removal, then steam-drying
and avoid over-drying
• Avoid unnecessary stand by use of steam systems
 Install air-atomizing and low-nitrogen-oxide (NOx) burners for oil-
fired boiler systems.
 Install automatic boiler blow-down control.
 Conduct flue gas Test of boilers.
 Install an automatic flue damper to close the flue when it is not
firing.
 Install tabulators to improve heat transfer efficiency in older fire tube
boilers.
 Install low-excess air burners.
 Install condensing economizers.
 Install electric ignitions instead of pilot lights.
 Install an automatic combustion control system to monitor the
combustion of exit gases and adjust the fuel-air ratio to reduce
excess combustion air.
 Install isolation valves to isolate off-line boilers.
ENERGY CONSERVATION MEASURES FOR
BOILERS AND FIRED SYSTEMS
 Maintain insulation on the heat distribution system. Replace
insulation after system repair, and repair damaged insulation.
 Provide proper water treatment to reduce fouling.
 Replace central plant with distributed satellite systems.
 Downsize boilers with optimum burner size and forced draft
(FD) fans.
 Operate boilers at their peak efficiency; shut down large
boilers during summer and use smaller boilers.
 Install expansion tanks on hot-water systems that are properly
sized for the system.
 Employ heat recovery through desuperheating.
 Preheat combustion air, feed water, or fuel oil with reclaimed
waste heat from boiler blowdown and/or flue gases.
 Install automatic controls to treat boiler makeup water.
 Check steam trap sizes to verify they are adequately sized to
provide proper condensate removal.
 Adjust boilers and air-conditioner controls so that boilers do not
fire and compressors do not start at the same time but satisfy
demand.
 Clean boiler surfaces regularly to reduce scale and deposit,
which will improve heat transfer.
 Replace noncondensing boilers with condensing boilers (15%–
20% higher efficiency when compared to new noncondensing
boilers).
 Prevent dumping steam condensate to drain.
 Survey and fix steam/hot-water/condensate leaks and failed
steam traps.
 Convert steam system to low-temperature sliding temperature
hot-water system. Install complementing steam boilers where
needed.
 Improve boiler insulation. It is possible to use new materials
that insulate better and have lower heat capacity.
 Boiler Horse Power (HP):
BHP = (Lb/hr) * FE/34.5
Where Lb/hr is pounds of steam per hour and FE is the
factor of evaporation.
 Cycle of Concentration of Boiler Water:
CYC = Bch / FCh
Where Bch is ppm water chlorides and FCh is ppm feed
water chloride.
 Deferential Setting (lb):
Delta s = p1 – p2
Where p1 is the cutout pressure and p2 is the cut in
pressure.
FORMULAS
 Factor of Evaporation:
FE = SH + LH / 970.3
Where SH is the sensible heat and LH is the latent heat.
 Force (lb):
F = P/A
Where P is pressure (psi) and A is area (ln^2).
 Horsepower (HP):
HP = (d * t) / (t * 33000)
Where d is distance, Fis force, and t is time.
 Inches of Mercury (in):
lnHG = p / 0.491
Where p is pressure.
 Percent of Blowdown:
%BD = (PP - RP) / PP
Where PR is popping pressure and RP is Reseat pressure
 Rate of Combustion (Btu/hr
RC=H / (Vf * t)
Where H is heat released (BTU), Vf is volume of
furnace (ft^3), and t is time (hr).
 Return condensate Percentage in feedwater
RC% = (MC - FC) / (MC – CC)
Where MC is the makeup conductivity (μohms).
 Static Head pressure (lb)
SHP = Bpr * 2.31
Where Bpr = boiler preesure (psi)
 Steam:
S = HP * 34.5 * t
Where HP is Boiler horsepower and t is time (h).
 Temperature Conversions:
F to C
C = (F – 32) / 1.8
C to F
F = (1.8 * C) + 32
 Total Force (lb):
TF = P * A
Where P is pressure (psi) and A is the area of valve
disc exposed to steam (sq.in.)
 Water Column (ln):
WC = P / 0.03061
Where P is pressure (psi)
Boiler, Steam Trapes,  Insulation and Steam Distribution System

Contenu connexe

Tendances

Gas Turbine Training Power Point -Sample
Gas Turbine Training Power Point -SampleGas Turbine Training Power Point -Sample
Gas Turbine Training Power Point -SampleAli Rafiei
 
Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul Manohar Tatwawadi
 
THERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONSTHERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONSManohar Tatwawadi
 
A Brief Introduction to Boilers
A Brief Introduction to BoilersA Brief Introduction to Boilers
A Brief Introduction to BoilersSATYAKAM MOHAPATRA
 
Operation and Maintenance of Diesel Power Generating Plants
Operation and Maintenance of Diesel Power Generating PlantsOperation and Maintenance of Diesel Power Generating Plants
Operation and Maintenance of Diesel Power Generating PlantsLiving Online
 
Steam Turbine Performance in TPS
Steam Turbine Performance in TPSSteam Turbine Performance in TPS
Steam Turbine Performance in TPSManohar Tatwawadi
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsSHIVAJI CHOUDHURY
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boilerKongkiert Tankayura
 
Boiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingBoiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingTahoor Alam Khan
 
Hydrogen Purge and Fill
Hydrogen Purge and FillHydrogen Purge and Fill
Hydrogen Purge and FillShad Edwards
 

Tendances (20)

Gas turbines
Gas turbinesGas turbines
Gas turbines
 
Steam leakage
Steam leakageSteam leakage
Steam leakage
 
Gas Turbine Training Power Point -Sample
Gas Turbine Training Power Point -SampleGas Turbine Training Power Point -Sample
Gas Turbine Training Power Point -Sample
 
Boiler Performance Monitoring
Boiler Performance MonitoringBoiler Performance Monitoring
Boiler Performance Monitoring
 
Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul Boiler recommissioning procedure after capital overhaul
Boiler recommissioning procedure after capital overhaul
 
THERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONSTHERMAL POWER PLANT OPERATIONS
THERMAL POWER PLANT OPERATIONS
 
FAQ on Turbines Part 2
FAQ on Turbines Part 2FAQ on Turbines Part 2
FAQ on Turbines Part 2
 
A Brief Introduction to Boilers
A Brief Introduction to BoilersA Brief Introduction to Boilers
A Brief Introduction to Boilers
 
Operation and Maintenance of Diesel Power Generating Plants
Operation and Maintenance of Diesel Power Generating PlantsOperation and Maintenance of Diesel Power Generating Plants
Operation and Maintenance of Diesel Power Generating Plants
 
Cooling water (CW) system
Cooling water (CW) system Cooling water (CW) system
Cooling water (CW) system
 
Unit protection scheme
Unit protection schemeUnit protection scheme
Unit protection scheme
 
Steam Turbine Performance in TPS
Steam Turbine Performance in TPSSteam Turbine Performance in TPS
Steam Turbine Performance in TPS
 
Boiler Introduction
Boiler IntroductionBoiler Introduction
Boiler Introduction
 
Pptfbc
PptfbcPptfbc
Pptfbc
 
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plants
 
Boiler Maintenance & Safety
Boiler Maintenance & SafetyBoiler Maintenance & Safety
Boiler Maintenance & Safety
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boiler
 
Boiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & WorkingBoiler Purging-Logic, Importance & Working
Boiler Purging-Logic, Importance & Working
 
Hydrogen Purge and Fill
Hydrogen Purge and FillHydrogen Purge and Fill
Hydrogen Purge and Fill
 

En vedette

Waste heat recovery
Waste heat recoveryWaste heat recovery
Waste heat recoveryAneel Ahmad
 
Waste Heat Recovery Vinay Shukla
Waste Heat Recovery  Vinay ShuklaWaste Heat Recovery  Vinay Shukla
Waste Heat Recovery Vinay ShuklaVinay Shukla
 
Pumps and pumping system
Pumps and pumping systemPumps and pumping system
Pumps and pumping systemWasiullah Khan
 
Energy management & audit
Energy management & auditEnergy management & audit
Energy management & auditPINAKI ROY
 
Plant layout and its types
Plant layout and its typesPlant layout and its types
Plant layout and its typesHammaduddin
 
Pumps and types of pumps in detail
Pumps and types of pumps in detailPumps and types of pumps in detail
Pumps and types of pumps in detailFARRUKH SHEHZAD
 

En vedette (8)

Waste heat recovery
Waste heat recoveryWaste heat recovery
Waste heat recovery
 
Waste heat recovery
Waste heat recoveryWaste heat recovery
Waste heat recovery
 
Waste Heat Recovery Vinay Shukla
Waste Heat Recovery  Vinay ShuklaWaste Heat Recovery  Vinay Shukla
Waste Heat Recovery Vinay Shukla
 
Pumps and pumping system
Pumps and pumping systemPumps and pumping system
Pumps and pumping system
 
Cogeneration Concept
Cogeneration ConceptCogeneration Concept
Cogeneration Concept
 
Energy management & audit
Energy management & auditEnergy management & audit
Energy management & audit
 
Plant layout and its types
Plant layout and its typesPlant layout and its types
Plant layout and its types
 
Pumps and types of pumps in detail
Pumps and types of pumps in detailPumps and types of pumps in detail
Pumps and types of pumps in detail
 

Similaire à Boiler, Steam Trapes, Insulation and Steam Distribution System

How to improve the efficiency of water tube boiler
How to improve the efficiency of water tube boilerHow to improve the efficiency of water tube boiler
How to improve the efficiency of water tube boilerMd Rabiul Hasan
 
STEAM GENERATORS.pptx
STEAM GENERATORS.pptxSTEAM GENERATORS.pptx
STEAM GENERATORS.pptxssusere6313f
 
Steam Generator or Boilers
Steam Generator or BoilersSteam Generator or Boilers
Steam Generator or BoilersRidwanul Hoque
 
Steam boilers
Steam boilersSteam boilers
Steam boilerssing367
 
MET 401 Chapter 4 boilers_and_steam_generators
MET 401 Chapter 4 boilers_and_steam_generatorsMET 401 Chapter 4 boilers_and_steam_generators
MET 401 Chapter 4 boilers_and_steam_generatorsIbrahim AboKhalil
 
UNIT-1-Steam Power Plant.pptx
UNIT-1-Steam Power Plant.pptxUNIT-1-Steam Power Plant.pptx
UNIT-1-Steam Power Plant.pptxprakash0712
 
Steam Boilers OR Steam Generators
Steam Boilers OR Steam GeneratorsSteam Boilers OR Steam Generators
Steam Boilers OR Steam GeneratorsHrishikesh Devan
 
Study of Boilers for Mechanical Engineering
Study of Boilers for Mechanical EngineeringStudy of Boilers for Mechanical Engineering
Study of Boilers for Mechanical EngineeringAbdullahKafi18
 
B.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilersB.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilersRai University
 
B.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilersB.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilersRai University
 
Ipe301 e steam generation unit
Ipe301 e steam generation unitIpe301 e steam generation unit
Ipe301 e steam generation unitK. M.
 
Introduction of Boiler
Introduction of BoilerIntroduction of Boiler
Introduction of BoilerMarine Study
 
Water and fire tube boilers
Water and fire tube boilersWater and fire tube boilers
Water and fire tube boilersTariq Jamshaid
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Steam-Power-Plant-updated.pdf engineering students
Steam-Power-Plant-updated.pdf engineering studentsSteam-Power-Plant-updated.pdf engineering students
Steam-Power-Plant-updated.pdf engineering studentsashokpradhan23
 

Similaire à Boiler, Steam Trapes, Insulation and Steam Distribution System (20)

How to improve the efficiency of water tube boiler
How to improve the efficiency of water tube boilerHow to improve the efficiency of water tube boiler
How to improve the efficiency of water tube boiler
 
Steam generator (boiler) vamshi
Steam generator (boiler) vamshiSteam generator (boiler) vamshi
Steam generator (boiler) vamshi
 
STEAM GENERATORS.pptx
STEAM GENERATORS.pptxSTEAM GENERATORS.pptx
STEAM GENERATORS.pptx
 
steam boilers.pptx
steam boilers.pptxsteam boilers.pptx
steam boilers.pptx
 
Steam Generator or Boilers
Steam Generator or BoilersSteam Generator or Boilers
Steam Generator or Boilers
 
Steam boilers
Steam boilersSteam boilers
Steam boilers
 
MET 401 Chapter 4 boilers_and_steam_generators
MET 401 Chapter 4 boilers_and_steam_generatorsMET 401 Chapter 4 boilers_and_steam_generators
MET 401 Chapter 4 boilers_and_steam_generators
 
UNIT-1-Steam Power Plant.pptx
UNIT-1-Steam Power Plant.pptxUNIT-1-Steam Power Plant.pptx
UNIT-1-Steam Power Plant.pptx
 
Steam power plant 2
Steam power plant 2Steam power plant 2
Steam power plant 2
 
Steam Boilers OR Steam Generators
Steam Boilers OR Steam GeneratorsSteam Boilers OR Steam Generators
Steam Boilers OR Steam Generators
 
Study of Boilers for Mechanical Engineering
Study of Boilers for Mechanical EngineeringStudy of Boilers for Mechanical Engineering
Study of Boilers for Mechanical Engineering
 
B.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilersB.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilers
 
B.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilersB.tech i eme u 2 steam boilers
B.tech i eme u 2 steam boilers
 
Boilers_report_final
Boilers_report_finalBoilers_report_final
Boilers_report_final
 
boilers
boilersboilers
boilers
 
Ipe301 e steam generation unit
Ipe301 e steam generation unitIpe301 e steam generation unit
Ipe301 e steam generation unit
 
Introduction of Boiler
Introduction of BoilerIntroduction of Boiler
Introduction of Boiler
 
Water and fire tube boilers
Water and fire tube boilersWater and fire tube boilers
Water and fire tube boilers
 
Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)Welcome to International Journal of Engineering Research and Development (IJERD)
Welcome to International Journal of Engineering Research and Development (IJERD)
 
Steam-Power-Plant-updated.pdf engineering students
Steam-Power-Plant-updated.pdf engineering studentsSteam-Power-Plant-updated.pdf engineering students
Steam-Power-Plant-updated.pdf engineering students
 

Dernier

Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxsiddharthjain2303
 
『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书
『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书
『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书rnrncn29
 
"Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ..."Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ...Erbil Polytechnic University
 
Module-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdfModule-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdfManish Kumar
 
Immutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfImmutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfDrew Moseley
 
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTESCME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTESkarthi keyan
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmDeepika Walanjkar
 
Theory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdfTheory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdfShreyas Pandit
 
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHTEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHSneha Padhiar
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionMebane Rash
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
 
Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...
Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...
Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...Sumanth A
 
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMSHigh Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMSsandhya757531
 
Robotics Group 10 (Control Schemes) cse.pdf
Robotics Group 10  (Control Schemes) cse.pdfRobotics Group 10  (Control Schemes) cse.pdf
Robotics Group 10 (Control Schemes) cse.pdfsahilsajad201
 
Cost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionCost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionSneha Padhiar
 
2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.
2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.
2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.elesangwon
 
List of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdfList of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdfisabel213075
 
Artificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewArtificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewsandhya757531
 
Secure Key Crypto - Tech Paper JET Tech Labs
Secure Key Crypto - Tech Paper JET Tech LabsSecure Key Crypto - Tech Paper JET Tech Labs
Secure Key Crypto - Tech Paper JET Tech Labsamber724300
 

Dernier (20)

Energy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptxEnergy Awareness training ppt for manufacturing process.pptx
Energy Awareness training ppt for manufacturing process.pptx
 
『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书
『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书
『澳洲文凭』买麦考瑞大学毕业证书成绩单办理澳洲Macquarie文凭学位证书
 
"Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ..."Exploring the Essential Functions and Design Considerations of Spillways in ...
"Exploring the Essential Functions and Design Considerations of Spillways in ...
 
Module-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdfModule-1-(Building Acoustics) Noise Control (Unit-3). pdf
Module-1-(Building Acoustics) Noise Control (Unit-3). pdf
 
Immutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdfImmutable Image-Based Operating Systems - EW2024.pdf
Immutable Image-Based Operating Systems - EW2024.pdf
 
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTESCME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
CME 397 - SURFACE ENGINEERING - UNIT 1 FULL NOTES
 
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithmComputer Graphics Introduction, Open GL, Line and Circle drawing algorithm
Computer Graphics Introduction, Open GL, Line and Circle drawing algorithm
 
Theory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdfTheory of Machine Notes / Lecture Material .pdf
Theory of Machine Notes / Lecture Material .pdf
 
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACHTEST CASE GENERATION GENERATION BLOCK BOX APPROACH
TEST CASE GENERATION GENERATION BLOCK BOX APPROACH
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of Action
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
 
Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...
Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...
Robotics-Asimov's Laws, Mechanical Subsystems, Robot Kinematics, Robot Dynami...
 
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMSHigh Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
High Voltage Engineering- OVER VOLTAGES IN ELECTRICAL POWER SYSTEMS
 
Robotics Group 10 (Control Schemes) cse.pdf
Robotics Group 10  (Control Schemes) cse.pdfRobotics Group 10  (Control Schemes) cse.pdf
Robotics Group 10 (Control Schemes) cse.pdf
 
Cost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based questionCost estimation approach: FP to COCOMO scenario based question
Cost estimation approach: FP to COCOMO scenario based question
 
Designing pile caps according to ACI 318-19.pptx
Designing pile caps according to ACI 318-19.pptxDesigning pile caps according to ACI 318-19.pptx
Designing pile caps according to ACI 318-19.pptx
 
2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.
2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.
2022 AWS DNA Hackathon 장애 대응 솔루션 jarvis.
 
List of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdfList of Accredited Concrete Batching Plant.pdf
List of Accredited Concrete Batching Plant.pdf
 
Artificial Intelligence in Power System overview
Artificial Intelligence in Power System overviewArtificial Intelligence in Power System overview
Artificial Intelligence in Power System overview
 
Secure Key Crypto - Tech Paper JET Tech Labs
Secure Key Crypto - Tech Paper JET Tech LabsSecure Key Crypto - Tech Paper JET Tech Labs
Secure Key Crypto - Tech Paper JET Tech Labs
 

Boiler, Steam Trapes, Insulation and Steam Distribution System

  • 2. BOILER: A boiler is defined as "a closed vessel in which water or other liquid is heated, steam or vapor is generated, steam is superheated, or any combination , under pressure or vacuum, for use external to itself, by the direct application of energy from the combustion of fuels, from electricity or nuclear energy." Types of Boiler: 1) Fire Tube Boiler 2) Water Boiler
  • 3. Fire Tube Boiler: The fire tube boiler design uses tubes to direct the hot gases from the combustion process through the boiler to a safe point of discharge. The tubes are submerged in the boiler water and transfer the heat from the hot gases into the water. Types of fire-tube boiler • Cornish boiler. • Lancashire boiler. • Scotch marine boiler. • Locomotive boiler. • Vertical fire-tube boiler. • Horizontal return tubular boiler. • Immersion fired boiler.
  • 4. • Cornish boiler : Cornish boiler is a simple horizontal boiler which belong to the shell and tube class of boilers. Cornish boiler is much like the Lancashire boiler. Cornish boiler has the ability to produce steam at the rate of 1350 kg/hr and can take the maximum pressure of about 12 bar. Dimensions of the Cornish boiler shell is 4 m to 7 m in length and 1.2 m to 1.8 m in diameter. • Lancashire boiler: The Lancashire boiler is similar to the Cornish, but has two large flues containing the fires instead of one. It is generally considered to be the invention of William Fairbairn in 1844, although his patent was for the method of firing the furnaces alternately, so as to reduce smoke, rather than the boiler itself.
  • 5. • Scotch Marine Boiler: The Scotch Marine Boiler is a fire-tube boiler, in that hot flue gases pass through tubes set within a tank of water. The general layout is that of a squat horizontal cylinder. One or more large cylindrical furnaces are in the lower part of the boiler shell. Above this is a large number of small-diameter fire-tubes. • Locomotive boiler: Locomotive boiler is the horizontal fire tube boiler in which hot gases pass through the tubes and water surrounds them. Transferred heat from the gases to water and then converted into steam. It may also be used as a stationary boiler.
  • 6. • Vertical fire-tube boiler : A vertical fire-tube boiler or vertical multitubular boiler is a vertical boiler where the heating surface is composed of multiple small fire-tubes, arranged vertically. These boilers were not common, owing to drawbacks with excessive wear in service. The more common form of vertical boiler, which was very similar in external appearance, instead used a single flue and water-filled cross-tubes. • Horizontal return tubular boiler: A fire-tube boiler is a type of boiler in which hot gases from a fire pass through one or (many) more tubes running through a sealed container of water. The heat of the gases is transferred through the walls of the tubes by thermal conduction, heating the water and ultimately creating steam.
  • 7. • The immersion fired boiler: The immersion fired boiler is a single-pass fire-tube boiler that was developed by Sellers Engineering in the 1940s. It has only firetubes, functioning as a furnace and combustion chamber also, with multiple burner nozzles injecting premixed air and natural gas under pressure. It claims reduced thermal stresses, and lacks refractory brickwork completely due to its construction
  • 8. Water Tube Boiler: The water tube boiler design uses tubes to direct the boiler water through the hot gases from the combustion process, allowing the hot gases to transfer its heat through the tube wall into the water. The boiler water flows by convection from the lower drum to the upper drum. Types of Water Tube Boiler: • Horizontal Straight Tube Boiler. • Bent Tube Boiler. • Cyclone Fired Boiler
  • 9. Burner is a mechanical device that burns a gas or liquid fuel into a flame in a controlled manner. Energy Efficient Burner: An efficient burner provides the proper air-to-fuel mixture throughout the full range of firing rates, without constant adjustment. Many burners with complex linkage designs do not hold their air-to-fuel settings over time. Often, they are adjusted to provide high excess air levels to compensate for inconsistencies in the burner performance. BURNER
  • 10. Energy Saving Due to Installation of an Energy Efficient Burner Burner Combustion Efficiency Improvement % Annual Energy Savings (MMBtu/year) Annual Savings ($) 1 6,250 28,125 2 12,345 55,550 3 18,290 82,305 Cost Savings = Fuel Consumption * Fuel Price * (1-E1/E2) If the installed cost is $50,000 for a new burner that provides an efficiency improvement of 2%, the simple payback on Investment is: Simple Payback = $50,000 ÷ $55,550/ year = 0.9 Years Example; Even a small Improvement in burner efficiency can provide significant savings. Consider a 50,000 pound per hour process boiler with a combustion efficiency of 79% (E1). The Boiler annually consumes 500,000 million British thermal units(MMBtu) of natural gas. At a price of $4.50/MMBtu, the annual fuel cost is $2.25million. What are the saving from installing an energy efficient burner that improves combustion efficiency by 1%, 2%, or 3 %.
  • 11. • Perform burner maintenance and tune your boiler. • Conduct combustion-efficiency tests at full- and part-load conditions. • If the excess O2 exceeds 3%, or combustion efficiency values are low, consider modernizing the fuel/air control system to include solid-state sensors and controls without linkage. Also consider installing improved process controls, an oxygen trim system, or a new energy-efficient burner. • A new energy-efficient burner should also be considered if repair costs become excessive, reliability becomes an issue, energy savings are guaranteed, and/or utility energy-conservation rebates are available. • Install a smaller burner on a boiler that is oversized relative to its steam load. SUGGESTED ACTIONS
  • 12.
  • 13. • Air Properties: For a burner originally adjusted to 15 % air, changes in combustion air temperature and barometric pressure cause the following in excess air: Expressed as a percent of the stoichiometric air required.
  • 14.
  • 15. PASSES OF BOILERS Three-pass firetube boiler: A 3-pass firetube boiler design consists of three sets of horizontal tubes, with the stack outlet located on the rear of the boiler. A downdraft design keeps the cooler water from having an effect on the hot surfaces within the boiler. 3 pass firetube boilers offer: • maximized heat transfer • minimal refractory • high steam/water storage • effective handling of wide load demands
  • 16. Four-pass boiler: A four-pass boiler design consists of four sets of horizontal tubes, with the stack outlet at the front of the vessel. A downdraft design keeps the cooler water from having an effect on the hot surfaces within the boiler. 4-pass boilers leverage natural draft operation which allows cool water to contact the hottest part of the boiler. 4 pass firetube boilers offer: • maximized heat transfer • minimal refractory • high steam/water storage • effective handling of wide load demands
  • 17. BOILER PERFORMANCE TEST Performance of the boiler, like efficiency and evaporation ratio reduces with time, due to poor combustion, heat transfer fouling and poor operation and maintenance. Deterioration of fuel quality and water quality also leads to poor performance of boiler. Efficiency testing helps us to find out how far the boiler efficiency drifts away from the best efficiency. • To find out the efficiency of the boiler • To find out the Evaporation ratio The purpose of the performance test is to determine actual performance and efficiency of the boiler and compare it with design values or norms. It is an indicator for tracking day-to-day and season- to-season variations in boiler efficiency and energy efficiency improvements 1. Boiler Efficiency = Heat Output/Heat Input*100 = Heat In Steam Output(kCals)/Heat in fuel Input(kCals)*100 2. Evaporation Ratio = Quantity of Steam Generation/Quantity of Fuel Consumption
  • 18.
  • 19. Heat recovery equipment is available to preheat feed water entering the boiler (economizer) and to capture Btu’s lost through boiler blowdown (blowdown heat recovery or flash tank heat exchangers). Such equipment is normally used on installations where boiler size, operating pressures or the amount of water make-up justify the economics for the purchase and installation costs (normally units exceeding 100 hp and operating at 100 psi or more). Maintenance costs also must be considered before a decision is made for their installation. HEAT RECOVERY EQUIPMENT
  • 20. Economizers are bent, finned-tube heat exchangers. They are available in rectangular or cylindrical styles. The type of boiler and the overall boiler room layout may dictate which style is utilized. The products of combustion leaving the boiler flow through the economizer, over the finned tubes, transferring its heat or Btu’s to the boiler feed water. The efficiency of the overall system can be increased By 2% to 4%, depending on fuel being burned, boiler size, and operating conditions. ECONOMIZERS
  • 21. There are several methods and equipment used in blowdown heat recovery. In most cases, the systems are used on continuous or surface blowdown to control the Total Dissolved Solids (TDS) in the boiler water. Blowdown heat recovery equipment is used for automatic control of the continuous blowdown, based on water make-up and cools the continuous blowdown to a point where it can be safely dumped to the sewer system. It transfers heat or Btu’s to the make-up water, thus raising the temperature of the make- up water before it enters the deaerator or boiler feed system. BLOWDOWN EQUIPMENT
  • 22. An additional piece of equipment, the blowdown separator , can be installed for bottom blowdown. The blowdown separator reduces the temperature of the bottom blowdown water to a temperature that would be safe for the sewer system. However, because of the erratic flow of bottom blowdown, there is little benefit to use a blowdown separator as a means to raise the temperature of make-up water prior to entering the deaerator or boiler feed system. BLOWDOWN SEPARATOR
  • 23. Another system uses the addition of a flash tank heat exchanger. This system works on the same principle as the blowdown heat recovery system, however, it also provides the benefit of flash steam. This flash steam can be reused in the plant, such as being piped to a deaerator and mixed with the incoming steam in the deaerator. FLASH TANK HEAT EXCHANGER:
  • 24. During daily operation of a plant, a sample cooler is normally required to draw samples of boiler water, so chemical tests can be performed. The boiler water, however, is above the temperature that test equipment can handle. In most cases, the situation is resolved with the installation of a sample cooler. SAMPLE COOLER
  • 25. Boiler feed water usually contains two harmful dissolved gases: Oxygen and Carbon Dioxide. If the dissolved gases are not removed before entering the boiler, they will be liberated by heat and may cause severe corrosion in the boiler, steam lines, condensate lines, and heat transfer equipment, which can prove to be very costly. The dissolved oxygen and carbon dioxide can be removed with chemicals. Depending on the overall system, it may not be practical to chemically remove the dissolved oxygen and carbon dioxide from the feed water. In these cases, a deaerator should be installed. Because the deaerator mechanically removes dissolved oxygen and carbon dioxide, the amount of chemicals required could be reduced. BOILER FEEDWATER EQUIPMENT
  • 26. The deaerator is a pressurized American Society of Mechanical Engineers (ASME) tank and may be the largest piece of auxiliary equipment in the boiler room. A deaerator is designed to heat water to the temperature of saturated steam at the pressure within the deaerator. A deaerator provides an effective means for recovery of heat from exhaust or flash steam, provides a location for returning condensate and accepts condensate first to reduce excessive make-up water. There are three types of deaerators available. The tray type is normally used in large utility plants. DEAERATORS
  • 27. If plant conditions do not warrant the use of a deaerator, in most cases, a Packaged Feed System is used. The packaged feed system is an atmospheric tank that can heat feed water to a maximum of 210°F. Because they are atmospheric tanks, they are equipped with an epoxy lining or made from galvanized steel. The packaged feed system heats the feed water and reduces the amount of dissolved oxygen and carbon dioxide in the feed water. There are many additional pieces of equipment available to remove impurities in the make-up water before it enters the boiler and system. The type of equipment required is determined by a water analysis. This equipment can be classified as pre-treatment equipment. FEED SYSTEMS
  • 28. Filters are available to remove free chlorine, some dissolved organics and sediment. They can also remove suspended solids, colloidal matter, sand and iron. There are carbon filters, multilayered filters, sand or iron filters. There can be lined tanks, American Society of Mechanical Engineers (ASME) code tanks and automatic operation based on a time clock, pressure differential switch or water meter. They can protect such items as water softeners, dealkalizers, and reverse osmosis equipment, etc. PRE-TREATMENT EQUIPMENT:
  • 29. A surge tank could be used under the following conditions: If there are intermittent peak loads of condensate that can exceed the surge capacity of the deaerator - varying pressures or temperatures in condensate – gravity or pumped condensate that have insufficient pressure to enter the deaerator on their own. Surge tanks are atmospheric and accept condensate and make-up water before it goes to the deaerator. Surge tanks can be lined with an epoxy coating to prevent corrosion. The condensate and make- up water mix into a blend temperature as determined by the percentage of each. SURGE TANK
  • 30. The Flame Safeguard or Programming Control on boilers are designed to ensure that the start-up of the burner follows a definite timed sequence of operation. In addition to the sequence of operation and after the flame has been established, the Flame Safeguard monitors the flame and sets the firing rate of the burner, as determined by the boiler firing rate controls. They also monitor, through the boiler controls, items such as boiler pressure or temperature, fuel pressure or temperature and they provide for normal shut down of the burner if the load demand is satisfied, or shut down and alarm if there is a safety shut down condition. The Flame Safeguards or Programming Control installed on a boiler can be classified into three categories: o Electro Mechanical o Solid State Electronic o Micro Processor FLAME SAFEGUARD EQUIPMENT
  • 31. The electro mechanical controls have been used from around 1950 until 1984. Solid state electronic controls were introduced in 1984. This type of control provides for more alarm or monitoring functions than the electro mechanical controls. The micro processor controls introduced in 1989 not only provide the functions as the other controls, but also have the ability to send information to computers and work in conjunction with some energy management systems. The micro processor type of controls are standardly furnished on some of today’s modern boilers. Solid state electronic controlsElectro mechanical controls
  • 32. After the initial inspection is completed, the new boiler is ready for startup. Startup can be the most critical period in the life of the boiler. 1. Steam piping, blow off and blowdown lines, etc. must be inspected and ready for operation. All piping must be inspected for adequate support and expansion provisions. 2. All fuel supply lines must be checked for tightness and leaks. Strainers are most important to the safe operation of gas and/or oil fired units. 3. Electrical power lines to the boiler/burner unit are connected and the voltage required is verified. 4. Hydrostatic test has been completed. 5. Any walkways, platforms, stairs, and/or ladders, etc., that are needed to permit proper access to the boiler/burner, are installed and ready for use. BOILER STARTUP
  • 33. Before the boiler is permitted to go on the line, all of the safety controls should be checked to make sure they are all operating properly. Flame Safeguard: The purpose of the flame safeguard control is to monitor the burner start up sequence, the main flame and control the firing rate during normal operation. Following is a brief step-by-step: 1. The burner switch is turned on or the operating limit pressure (or temperature) control closes. If all required limit controls are satisfied, the blower motor starts and the automatic sequence begins. 2. The programmer actuates the modulating motor and drives it to high fire position and purges the boiler for a predetermined period of time. 3. The programmer drives, modulating motor and burner linkage back to low fire position. BOILER CONTROLS
  • 34. 4. The ignition transformer is energized and the pilot solenoid valves are opened. The pilot must light. 5. Trial for ignition period. 6. If the pilot flame is proven, the programmer, after a timed interval, energizes the main flame fuel valve(s) and trial for main flame is started, at minimum fuel rate. 7. After a timed period, the main flame has to be established. If this is completed, the programmer extinguishes the pilot and then continues to monitor the main flame. 8. The programmer continues to monitor the main flame while the burner continues to automatically modulate (if the burner is capable of full modulation) on an increasing or decreasing firing rate to satisfy the load demand. 9. The programmer cycles to off position and is now ready for restart upon demand.
  • 35. 1. Know your equipment. 2. Maintain complete records. 3. Establish a regular boiler inspection schedule. The schedule should include daily, weekly, monthly, semi-annual and annual inspections or activities. 4. Establish and use boiler log sheets. Log sheets should be tailored to your equipment. 5. Establish and keep written operating procedures updated. 6. Good housekeeping is a must. 7. Keep electrical equipment clean. BOILER ROOM CARE
  • 36. 1. Check water level. Ensure there is water in the gauge glass every time you enter the boiler room. 2. Blow down boiler. Blow down the boiler in accordance with the recommendation of your feedwater consultant. 3. Blow down the water level controls to purge the float bowl of possible sediment accumulation. Operating conditions will dictate frequency of this check. 4. Check combustion visually. Look at the flame to see if something has changed. 5. Treat water according to the established program. Add chemicals and take tests as outlined by your chemical feedwater consultant. 6. Record boiler operating pressure or temperature. 7. Record feedwater pressure and temperature. 8. Record stack temperature. Changes in stack temperatures could indicate the boiler is sooting, scaling or there is a problem with baffles or refractory. DAILY MAINTENANCE
  • 37. 9. Record oil pressure and temperature. 10. Record oil atomizing pressure. Changes in pressure could have an effect on combustion in the boiler. 11. Record gas pressure. Changes in pressure could have an effect on combustion in the boiler and indicate a problem in the gas delivery system. 12. Check general boiler/burner operation. Maintaining top efficiency is the simple and basic reason for having operating personnel. Is anything different than it was the day before? If so, why? 13. Record boiler water supply and return temperatures. On hot water boilers, record these temperatures to assist in detecting system changes. 14. Record makeup water usage. Excessive makeup water could be an indication of system problems in both steam and hot water systems. 15. Check auxiliary equipment.
  • 38. 1. Check for tight closing of fuel valves. 2. Check fuel and air linkages. 3. Check indicating lights and alarms. 4. Check operating and limit controls. 5. Check safety and interlock controls. 6. Check operation of water level controls. 7. Check for leaks, noise, vibration, unusual conditions, etc. Checking for these items is a cost effective way to detect system operational changes. Small problems can be corrected before they become large problems. 8. Check operation of all motors. 9. Check lubricating levels. 10. Check the flame scanner assembly. 11. Check packing glands on all pumps and metering devices. 12. Check gauge glass. Ensure there are no cracks or etching in the glass or leakage around the packing. WEEKLY MAINTENANCE
  • 39. 1. Inspect burner operation. 2. Analyze combustion. 3. Check cams. Inspect the cam springs for scoring, tightness of set screws, free movement, alignment of cam followers and other related parts. 4. Check for flue gas leaks. 5. Inspect for hot spots. Inspect the boiler to ensure no hot spots are developing on the outside of the boiler. 6. Review boiler blowdown to determine that a waste of treated water is not occurring. 7. Check all combustion air supply inlets to the boiler room and burner to ensure sufficient air is being supplied. 8. Check all filter elements. Clean or replace as needed 9. Check the fuel system to make certain that strainers, vacuum gauges, pressure gauges and pumps are properly cared for. 10. Check all belt drives for possible failure. MONTHLY MAINTENANCE
  • 40. 1. Clean low water cutoff . Remove the head assembly or probes and inspect and clean out any sediment or contamination in the column or piping. 2. Check oil preheaters by removing the heating element and inspect for sludge or scale. 3. Repair refractory. Immediately upon opening the fireside areas, give the refractories an inspection and start repairs as soon as possible. 4. Clean oil pump strainer and filter. 5. Check pump coupling alignment. 6. Reset Combustion. The entire combustion process should be carefully checked, O2 readings taken and necessary burner adjustments made. 7. Inspect mercury switches. Inspect mercury switches for contamination, loss of mercury, and cracked or broken wires. Replace if any of these conditions are found. SEMI-ANNUAL MAINTENANCE
  • 41. 1. Clean fireside surfaces by brush or use a powerful vacuum cleaner to remove soot. 2. Clean breeching. Inspect breeching and stack and remove any soot build up. 3. Clean waterside surfaces. Remove all hand hole and manway plates, inspection plugs from water column tees and crosses and float assemblies from water columns. 4. Check fluid levels on all hydraulic valves. If any leakage is apparent, take positive corrective action immediately. 5. Check gauge glass for possible replacement. If internal erosion at water level is noted, replace with new glass and gaskets. 6. Remove and recondition safety valves. Have them reconditioned by an authorized safety valve facility. 7. If oil fuels are used, check on the condition of the fuel pump. Fuel pumps wear out and the annual inspection time is the opportune time to rebuild or replace them. ANNUAL MAINTENANCE
  • 42. 9. Boiler feed pumps. Strainers should be reconditioned. 10. Condensate receivers should be emptied and washed out. Make an internal inspection, if possible. 11. Chemical feed systems should be completely emptied, flushed and reconditioned. Metering valves or pumps should be reconditioned at this time. 12. Tighten all electrical terminals. All terminals should be checked for tightness, particularly on starters and movable relays. 13. Check linkages. Check to ensure the linkage ball connectors have not worn out. Worn connectors can cause inconstancy in the linkage movement and result in unrepeatable excess air levels in the combustion process.
  • 43. 1. The boiler room is for the boiler. The boiler room should not be considered an all-purpose storage area. The burner requires proper air circulation in order to prevent incomplete fuel combustion and production of carbon monoxide. Therefore, keep the boiler room clean and clear of all unnecessary items.1. 2. Knowledge is powerful, as are boilers. Ensure all personnel who operate or maintain the boiler room are properly trained on all equipment, controls, safety devices, and up-to-date operating procedures.1. 3. Look for potential problems. Before startup, ensure the boiler room is free of all possibly dangerous situations, such as flammable materials or mechanical or physical damage to the boiler or related equipment. Clear intakes and exhaust vents; check for deterioration and possible leaks. BOILER ROOM GUIDELINES
  • 44. 4. Observe new equipment. Monitor all new equipment closely until safety and efficiency are demonstrated. 4. Develop a maintenance schedule. Use boiler operating log sheets, maintenance records, and manufacturers’ recommendations to establish a preventive maintenance schedule based on operating conditions, as well as on past maintenance, repairs, and replacements performed on the equipment. 6. Inspection matters. Ensure a thorough inspection by a properly qualified inspector, such as one who holds a National Board commission. 7. Reinspection matters, too. After any extensive repair or new installation of equipment, make sure a qualified boiler inspector reexamines the entire system.
  • 45. 8. Create thorough checklists. Establish a checklist for proper startup and shutdown of boilers and all related equipment according to manufacturers’ recommendations. 9. Don’t overlook automated systems. Observe equipment extensively before allowing an automated operation system to be used with minimal supervision. 10. Keep safety at the forefront. Establish a periodic preventive maintenance and safety testing program.
  • 47. 1.) Points about the steam trap a. Mechanical steam trap b. (On/Off Operation) c. Test point – downstream of the discharge orifice 2.) Visual inspection a. Steam trap should be level to the eye b. Check flow arrow to insure steam trap is installed correctly 3.) Temperature measurement a. Take temperatures before and after steam trap b. Temperatures below 212°F or 100°C, steam trap is not in operation c. Take temperature at the process inlet. Temperatures at the process inlet and the steam trap inlet will be relatively close. 4.) Off position during operation a. Ultrasound level should be low or zero on the ultrasound meter b. Long off periods can cause “loss of prime”
  • 48. 5.) Discharge Operation (discharging condensate) a. When the inverted bucket drops due to the loss of buoyancy, this will bring the valve away from the discharge orifice. This action will allow the steam trap to discharge the condensate. b. The ultrasound indicator will rise due to the increase in ultrasound from the discharge cycle. The ultrasound will stay high or full scale until condensate is discharged from the steam trap. The ultrasound level (meter) should deflect more than 30% of scale. c. When condensate is completely discharged, the inverted bucket will rise, due to buoyancy, and bring the valve in contact with the discharge orifice .The steam trap is now in the off position. The ultrasound level should be at zero or minimum.
  • 49. d. Ultrasound level should proceed to full or high ultrasound level during the discharge cycle and return to minimum scale reading or zero after the discharge is complete. e. Condensate will crackle and steam will whistle during testing with the ultrasound equipment, therefore during the cycling there will be a crackling + whistling sound during the discharge cycle (steam and condensate passing through the orifice of the steam trap). f. The steam trap should stay in the off position for a least 15 seconds before cycling (less than 15 seconds if the steam trap is undersized) g. Discharge – ultrasound meter should increase the ultrasound level. h. The steam trap has a fast on/off operation. 6.) Light Condensate Load Operation a. Ultrasound levels will cycle on and off at low ultrasound levels. This is an indication of low condensate flows.
  • 50. 7.) Failure Modes a. Leaking steam Steam trap valve wear or linkage will cause the steam trap to leak steam. The following are indicators of leaking steam: • Ultrasound meter does not return to zero or baseline after condensate discharge cycle. • Ultrasound levels are continuous off base line and there is not distinct cycle/no cycle operation.
  • 51. b. Blowing steam Steam trap valve or linkage failure or over sizing (loss of prime) will cause the steam trap to blow steam directly through the steam trap. The following are indicators of leaking steam: • Ultrasound meter is at full scale. • Hearing a dominant whistling sound and no crackling.
  • 53. STEAM SYSTEMS IN INDUSTRY AND OTHER SECTORS • Steam can be used for heating, drying, moistening and sterilization of products in industry and other fields • Steam has advantages in effective heat transfer, indirect or direct heating and hygienic. • Special attention shall be given in productivity of steam production (exhaust gas and blowout losses), distribution networks and steam users. • Water treatment and high maintenance needs may increase operating costs.
  • 54. STEAM PRODUCTION • Steam can be produced by steam boilers and steam generators. • Key factors in economic steam production o boiler plant o continuous consumption monitoring o skilled personnel • Considerations in boilers o boiler capacity meets steam requirements o meters are in good condition o out-blow is not excessive o economizer is in operation o heat transfer surfaces are clean o boiler has no air leakages o boiler insulation is in good condition
  • 55. STEAM NETWORKS • Steam use can be either direct or indirect, but the used energy amount is the same, but heat losses may differ. • In direct use the valuable condensing water return shall be checked regularly • Superheated steam has lower heat transfer coefficient than saturated steam • Moist steam stress equipment more than dry steam • Air mixed in steam reduces the heat transfer coefficient
  • 56. LEAKAGES • Leaks in steam systems o waste continuously energy (24/7) o reduce network pressure and energy flow o waste valuable condense water (treated water) o reduce work safety (blasts) • To be checked visually or with ultrasonic detector o safety valves, steam traps, orifice connectors, gate valves, unattended pipe-tunnels o leakage inspections shall be made at least twice per year
  • 57. PIPE AND EQUIPMENT INSULATION • Pipes, flanges, equipment and valves shall be insulated because of heat losses and working safety • Condense pipes always insulated, except condense valves • Wet insulation causes energy waste and outside corrosion • Un-insulated DN 200 valve may have up to 200 C temperature and 5 kW continuous heat loss
  • 58. CONDENSE RETURN • Condense return is important in indirect steam use. Condense traps are important. • Precise condense return causes: o good utilization of condense heat content o reduction in make-up water needs • Closure of open condense tank causes o reduction in heat loss o reduction in tank corrosion • Condense tank should be blanketed from oxygen entry by steam etc
  • 59. FAILURES IN CONDENSE TRAPS • Condense return rate shall be monitored and maximized • Fault trap causes steam-condense mix in condense pipe leading to increased temperate and backpressure, increased steam consumption, higher condense and high feed water pumping costs • Faults in condense traps should be seek by listening (man / machine) and by temperature metering (every 2 to 4 months)
  • 60. UTILIZATION OF BLOWOUT STEAM • Benefits of blowout o Reduced steam consumption o Lost blowout steam reduces o Capacity of condensing network increases • Utilization of blowout steam o Blowout steam usage in low pressure systems o Preheating of combustion air, compressed air and rooms o Heating of sub-cooled condense or preheating of process-water in condense tank
  • 61. ECONOMICAL USE OF STEAM • Steam pressure o Is defined by required temperature /pressure level o It is important that temperature/pressure meets the user requirements o It is important that pressure fluctuation is as small as possible o Steam networks can be divided by pressure reduction valves to different pressure subnets
  • 62. EQUIPMENT CONSIDERATIONS • Very important that process automation works properly • Steam network and equipment shall be started slowly • Steam heated equipment shall have thermal insulation • Open liquid surfaces shall be covered against evaporation • Bypass valves shall be kept closed and watertight • Minimization of steam pressure, finally replacing steam with hot water • Drying first by mechanical water removal, then steam-drying and avoid over-drying • Avoid unnecessary stand by use of steam systems
  • 63.  Install air-atomizing and low-nitrogen-oxide (NOx) burners for oil- fired boiler systems.  Install automatic boiler blow-down control.  Conduct flue gas Test of boilers.  Install an automatic flue damper to close the flue when it is not firing.  Install tabulators to improve heat transfer efficiency in older fire tube boilers.  Install low-excess air burners.  Install condensing economizers.  Install electric ignitions instead of pilot lights.  Install an automatic combustion control system to monitor the combustion of exit gases and adjust the fuel-air ratio to reduce excess combustion air.  Install isolation valves to isolate off-line boilers. ENERGY CONSERVATION MEASURES FOR BOILERS AND FIRED SYSTEMS
  • 64.  Maintain insulation on the heat distribution system. Replace insulation after system repair, and repair damaged insulation.  Provide proper water treatment to reduce fouling.  Replace central plant with distributed satellite systems.  Downsize boilers with optimum burner size and forced draft (FD) fans.  Operate boilers at their peak efficiency; shut down large boilers during summer and use smaller boilers.  Install expansion tanks on hot-water systems that are properly sized for the system.  Employ heat recovery through desuperheating.  Preheat combustion air, feed water, or fuel oil with reclaimed waste heat from boiler blowdown and/or flue gases.  Install automatic controls to treat boiler makeup water.  Check steam trap sizes to verify they are adequately sized to provide proper condensate removal.
  • 65.  Adjust boilers and air-conditioner controls so that boilers do not fire and compressors do not start at the same time but satisfy demand.  Clean boiler surfaces regularly to reduce scale and deposit, which will improve heat transfer.  Replace noncondensing boilers with condensing boilers (15%– 20% higher efficiency when compared to new noncondensing boilers).  Prevent dumping steam condensate to drain.  Survey and fix steam/hot-water/condensate leaks and failed steam traps.  Convert steam system to low-temperature sliding temperature hot-water system. Install complementing steam boilers where needed.  Improve boiler insulation. It is possible to use new materials that insulate better and have lower heat capacity.
  • 66.  Boiler Horse Power (HP): BHP = (Lb/hr) * FE/34.5 Where Lb/hr is pounds of steam per hour and FE is the factor of evaporation.  Cycle of Concentration of Boiler Water: CYC = Bch / FCh Where Bch is ppm water chlorides and FCh is ppm feed water chloride.  Deferential Setting (lb): Delta s = p1 – p2 Where p1 is the cutout pressure and p2 is the cut in pressure. FORMULAS
  • 67.  Factor of Evaporation: FE = SH + LH / 970.3 Where SH is the sensible heat and LH is the latent heat.  Force (lb): F = P/A Where P is pressure (psi) and A is area (ln^2).  Horsepower (HP): HP = (d * t) / (t * 33000) Where d is distance, Fis force, and t is time.  Inches of Mercury (in): lnHG = p / 0.491 Where p is pressure.
  • 68.  Percent of Blowdown: %BD = (PP - RP) / PP Where PR is popping pressure and RP is Reseat pressure  Rate of Combustion (Btu/hr RC=H / (Vf * t) Where H is heat released (BTU), Vf is volume of furnace (ft^3), and t is time (hr).  Return condensate Percentage in feedwater RC% = (MC - FC) / (MC – CC) Where MC is the makeup conductivity (μohms).  Static Head pressure (lb) SHP = Bpr * 2.31 Where Bpr = boiler preesure (psi)
  • 69.  Steam: S = HP * 34.5 * t Where HP is Boiler horsepower and t is time (h).  Temperature Conversions: F to C C = (F – 32) / 1.8 C to F F = (1.8 * C) + 32  Total Force (lb): TF = P * A Where P is pressure (psi) and A is the area of valve disc exposed to steam (sq.in.)  Water Column (ln): WC = P / 0.03061 Where P is pressure (psi)